FD and DFD 150X Series models are intended for
installation in accordance with fire damper requirements
established by:
National Fire Protection Association
NFPA Standard 90A
BOCA
National Building Codes
ICBO
Uniform Building Codes
IBC
International Building Codes
SBCCI Standard Building Codes
CSFM California State Fire Marshal
Fire Damper Listing (#3225-0981:102)
New York City (BSA/MEA listing #260-91-M)
"UL CLASSIFIED (see complete marking on product)"
"UL CLASSIFIED to Canadian safety standards (see
complete marking on product)"
UL Standard 555 (Listing #R13317)
RECEIVING AND HANDLING
Upon receiving dampers, check for both obvious and hidden damage. If
damage is found, record all necessary information on the bill of lading and
file a claim with the final carrier. Check to be sure that all parts of the
shipment, including accessories, are accounted for.
Dampers must be kept dry and clean. Indoor storage and protection from
dirt, dust and the weather is highly recommended. Do not store at
temperatures in excess of 100°F.
SAFETY WARNING:
Improper installation, adjustment, alteration, service or maintenance
can cause property damage, injury or death. Read the installation,
operating, and maintenance instructions thoroughly before installing
or servicing this equipment.
This manual is the property of the owner, and is required for future
maintenance. Please leave it with the owner when the job is complete.
Greenheck warrants this equipment to be free from defects in material and
workmanship for a period of one year from the purchase date. Any units or
parts which prove to be defective during the warranty period will be
repaired or replaced at our option. Greenheck shall not be liable for
damages resulting from misapplication or misuse of its products.
Greenheck will not be responsible for any installation or removal costs.
Greenheck will not be responsible for any service work or backcharges
without prior written authorization.
INSTALLATION SUPPLEMENTS
Refer to the appropriate Greenheck installation supplements
for special requirements:
Support Mullions
Shaftwall Supplement
Drywall Supplement
Grille Installation Supplement
Note: Refer to Greenheck IOM, Part #461335, for CFSD
models to be installed in corridor ceiling applications.
WARRANTY
Installation, Operation and
Maintenance Instructions
FD & DFD 150X
for
Curtain Fire Dampers
Vertical or Horizontal Mount
Maximum
6 in.
Duct
Retaining Angles
(See Section 3)
Duct
On types R & CR factory
furnished duct collar
qualifies as breakaway
connection.
Duct
Figure 1: Type A, Type B, and Type C,
CO, CR, R damper installation
diagrams.
Part #453946
MODELS
1
1
Hour
2
1/4 in.
minimum total
clearance
Wall or Floor
Maximum
6 in.
Damper
Type A
Wall or Floor
Damper
Type B
Wall or Floor
Damper
Type C, CO, CR & R

Advertisement

loading

Summary of Contents for Greenheck FD150X

  • Page 1 WARRANTY On types R & CR factory furnished duct collar Greenheck warrants this equipment to be free from defects in material and qualifies as breakaway connection. workmanship for a period of one year from the purchase date. Any units or parts which prove to be defective during the warranty period will be repaired or replaced at our option.
  • Page 2: Table Of Contents

    Table of Contents Pre-Installation Guidelines......................2 Installation............................3-4 Breakaway Connections........................5 Damper Maintenance........................6 Damper Troubleshooting........................6 Installation for Steel Stud Connection Option................6-7 Pre-Installation Guidelines The basic intent of a proper installation is to secure the fire damper in, not to, the opening in such a manner as to prevent distortion and disruption of damper operation.
  • Page 3: Installation

    Installation - Failure to follow these instructions will void all warranties. These instructions apply to 1 ⁄ hour rated fire dampers mounted in masonry, block or stud walls and concrete floors. Specific requirements in these instructions are mandatory. These instructions meet the requirements of UL 555. Installation shall comply with the requirements of NFPA 90A Standard for the Installation of Air Conditioning and Ventilating Systems.
  • Page 4 4. CONNECTING DUCTS TO THE FIRE DAMPER All duct connections to FD & DFD 150X series extended frame dampers must be “breakaway” type connections. All connections shown on page 24 in. o.c. 24 in. o.c. Ceiling Runner Maximum Maximum 6 are considered breakaway. Factory furnished (metal studs) (metal studs) duct collars on types R &...
  • Page 5: Breakaway Connections

    Breakaway Connections Traditional Breakaway Style Transverse Joints Transverse joints illustrated in Figure 5 have always Plain “S” Slip Hemmed “S” Slip Double “S” Slip been approved as breakaway connections. SMACNA testing has also approved the following variations as breakaway connections. •...
  • Page 6: Damper Maintenance

    Damper Maintenance Dampers shall be maintained, cycled, and tested in intervals as stated in the latest editions of NFPA 90A, 92A, and UL 864 unless local codes require more frequent inspections. Dampers do not typically require maintenance as long as they are kept dry and clean. If cleaning is necessary, use mild detergents or solvents.
  • Page 7 Retaining Top Cross-Section View Side Cross-Section View of Damper in Wall Due to continuing research, Greenheck reserves the right to change specifications without notice. GREENHECK IOM-FD/DFD-150X Series P.O. BOX 410 SCHOFIELD, WISCONSIN 54476-0410 Rev. 9 April 2004 PH.