1 1/2 hour fire & combination fire smoke dampers

Advertisement

Quick Links

Installation, Operation and Maintenance Instructions
INStALLAtION SUPPLEMENtS
Refer to the appropriate Greenheck installation
supplements for special requirements:
• Steel Deck Supplement
RECEIVING AND HANDLING
Upon receiving dampers, check for both obvious and
hidden damage. If damage is found, record all necessary
information on the bill of lading and file a claim with
the final carrier. Check to be sure that all parts of the
shipment, including accessories, are accounted for.
Dampers must be kept dry and clean. Indoor storage
and protection from dirt, dust and the weather is highly
recommended. Do not store at temperatures in excess of
100°F (38°C).
WARRANty
Greenheck warrants this equipment to be free from
defects in material and workmanship for a period of one
year from the purchase date. Any units or parts which
prove to be defective during the warranty period will be
repaired or replaced at our option. Greenheck shall not
be liable for damages resulting from misapplication or
misuse of its products. Greenheck will not be responsible
for any installation or removal costs. Greenheck will not
be responsible for any service work or backcharges
without prior written authorization.
Due to continuing research, Greenheck reserves the right to change specifications without notice.
This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when the
job is complete.
FSDR-XXX, SEFSDR-XXX,
AND SSFSDR-XXX MODELS
1
Hour Fire & Combination Fire
1
2
FSDR-XXX, SEFSDR-XXX, and SSFSDR-XXX Model
Dampers are intended for installation in accordance with
combination fire smoke damper requirements established
by:
National Fire Protection Association
NFPA Standards 80, 90A, 92A, 92B, 101, & 105
IBC International Building Codes
New york City (MEA listing #260-91-M)
"UL CLASSIFIED (see complete marking on product)"
"UL CLASSIFIED to Canadian safety standards (see
complete marking on product)"
UL Standard 555 & 555S (Classification #R13317)
ELECtRICAL GUIDELINES
All wiring shall be done in accordance with the National
Electrical Code ANSI/NFPA-70 latest edition, any local
codes that may apply, and wiring diagrams developed
in compliance with the job or project design and
specifications.
SAFEty WARNING
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, injury or
death. Read the installation, operating, and maintenance
instructions thoroughly before installing or servicing this
equipment. To avoid causing death or serious bodily harm
to building occupants, follow all instructions carefully.
Dampers must close completely to preserve the integrity
of the fire smoke separation.
SAFEty CAUtION!
Electrical input may be needed for this equipment. This
work should be performed by a qualified electrician.
Verify power before wiring actuator. Greenheck is not
responsible for any damage to, or failure of the unit
caused by incorrect field wiring.
Part Number 461868
Smoke Dampers
Vertical and Horizontal Mount

Advertisement

loading

Summary of Contents for Greenheck FSDR Series

  • Page 1 Due to continuing research, Greenheck reserves the right to change specifications without notice. This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when the...
  • Page 2: Table Of Contents

    table of Contents Pre-Installation Guideline ....................... 2 Installation ...........................3-6 • Clearances Required Between Fire Damper Sleeves and Wall/Floor Openings ..... 3 • Sleeve Length and Wall Thickness .....................3 • Round Duct Connections ......................3 • Securing the Damper Assembly to Wall and Floor Openings ..........4 •...
  • Page 3: Installation

    Installation - Failure to follow these instructions will void all warranties. These instructions apply to 11/2 hour rated combination fire smoke and fire dampers mounted (blades must be horizontal) in: 1) masonry, block or stud walls and 2) concrete floors or ceilings. Specific requirements in these instructions are mandatory.
  • Page 4: Securing The Damper Assembly To Wall And Floor Openings

    4. SECURING tHE DAMPER/SLEEVE ASSEMBLy tO WALL AND FLOOR OPENINGS Damper assemblies must be installed in wall/floor openings using a single retaining plate on either side of the wall/floor or by using a retaining plate on both sides of the wall/floor.
  • Page 5: Fsdr-Xxx And Dfdr-Xxx Blade Orientation

    6. CONNECtION AND OPERAtION OF tEMPERAtURE RESPONSE DEVICES (Fusible Link, RRL OPtION, OCI OPtION, tOR OPtION, and PRV OPtION) continued..OCI - The OCI (open or closed indicator) option contains a single pole, double throw switch used to indicate the damper blade position.
  • Page 6: Recommended Preparation Of Openings In Wood And Metal Stud

    RRL or TOR sensor tripped Heat Push reset button located on backside of RRL or TOR Damper does not operate No power supplied to the actuator Add power supply Copyright © 2008 Greenheck Fan Corporation 461868 FSDR-XXX Rev. 10 December 2008...

This manual is also suitable for:

Ssfsdr seriesSefsdr series