• Switch 5 can be used to invert the output signal of all electrical outputs.
• The SICLOCK PCON provides the option of monitoring all inputs or the
120 VDC voltage output. For this purpose, a check is made to determine
whether a status change takes place on the signal lines. If a steady signal of
an appropriate length is detected, an alarm contact is activated. Switch 6 can
be used to activate this monitoring function. Switch 7 is used to specify
whether the inputs or the output is to be monitored. Switch 8 can be used to
specify whether the alarm relay switches after 3 seconds or 3 minutes in the
event of a missing signal change.
Table 4-3
Switches
5
5
6
6
7
7
8
8
®
SICLOCK
PCON
Operating Instructions, 04/2012, A2B00056366E-01
Switches 5 to 8
Item
OFF
Electrical output signals not inverted
ON
Electrical output signals inverted
OFF
Monitoring deactivated
ON
Monitoring activated
OFF
Monitoring of inputs
ON
Monitoring of 120 VDC voltage output
OFF
Alarm after 3 seconds without signal change
ON
Alarm after 3 minutes without signal change
Significance
4-13