Climatic transport and storage conditions
The following information applies to a device that is transported in the original packaging and
weather-proof packaging, and stored from some time.
The device meets the requirements according to IEC 60721-3-2 Class 2K4 with the following
amendments and limitations:
Type of condition
Temperature
Atmospheric pressure,
altitude
Relative humidity
Pollutant concentration
Note
If dewing has developed, wait until the HMI device has dried completely before switching it
on.
Do not expose the HMI device to direct radiation from a heater.
5.5.2

Operating conditions

Mechanical and climatic conditions of use
The device is designed for use in locations protected from the effects of the weather. The
conditions of use meet the requirements for DIN IEC 60721-3-3:
● Class 3M3 (mechanical requirements)
● Class 3K3 (climatic requirements)
Mechanical ambient conditions
The mechanical ambient conditions for the device are specified in the table below in terms of
sinusoidal vibration.
Frequency range f in Hz
10 ... 58 Hz
58 ... 200 Hz
Siemens Drives & PLCs
IFP2200 INOX MT ETH
Compact Operating Instructions, 03/2018, A5E42185570-AA
Permitted range
–20 ... 60 °C
1140 ... 660 hPa, corresponds to an elevation of -1000 to 3500 m
10 ... 90 %
SO2: < 0.5 ppm; relative humidity < 60 %, no condensation
H
S: < 0.1 ppm; relative humidity < 60 %, no condensation
2
Constant
Amplitude 0.0375 mm
Constant acceleration 0.5 g
Technical specifications
5.5 Ambient conditions
Occasional
Amplitude 3.5 mm
Constant acceleration 1 g