Greenheck Microprocessor Controller Reference Manual page 49

For dedicated outdoor air system doas v3.001
Table of Contents

Advertisement

VARIABLE
DESCRIPTION
Supply_Air_
Supply Air Temperature
Temperature_Sensor_
Sensor Alarm (0=Normal
Alarm.Active
1=Alarm)
Supply_Duct_Static_
Supply Duct Static Pressure
Pressure_Analog_
Analog Input Alarm
Input_Alarm.Active
(0=Normal 1=Alarm)
Supply_Fan_1_Alarm.
Supply Fan 1 Alarm
Active
(0=Normal 1=Alarm)
Supply_High_Duct_
Supply High Duct Static
Static_Alarm.Active
Alarm (0=Normal 1=Alarm)
Supply_RH_Sensor_
Supply RH Sensor Alarm
Alarm.Active
(0=Normal 1=Alarm)
Supply_Temp_High_
Supply Temp High Limit
Limit_Alarm.Active
Alarm (0=Normal 1=Alarm)
TMem Error Alarm
TMem_Error.Active
(0=Normal 1=Alarm)
Wheel_Rotation_
Wheel Rotation Alarm
Alarm.Active
(0=Normal 1=Alarm)
EVD Battery Alarm
Al_Batt_EVD_1.Active
(0=Normal 1=Alarm)
Al_ConfigErr_EVD_1.
EVD Configuration Alarm
Active
(0=Normal 1=Alarm)
Compressor Envelope -
Al_DscgHiP_COMP_1.
High Discharge Pressure
Active
Alarm (0=Normal 1=Alarm)
Compressor Envelope
Al_DscgHiTemp_
- High Discharge
COMP_1.Active
Temperature Alarm
(0=Normal 1=Alarm)
EVD Low Discharge
Al_DscgLowP_
Pressure Alarm (0=Normal
COMP_1.Active
1=Alarm)
Al_EEPROM_EVD_1.
EVD EEPROM Alarm
Active
(0=Normal 1=Alarm)
Al_EEV_A_EVD_1.
ExV Motor Alarm - Valve 1
Active
(0=Normal 1=Alarm)
Al_EmergencyClosing_
EVD Emergency Closing
EVD_1.Active
Alarm (0=Normal 1=Alarm)
Al_EVD_Offline_
EVD Offline Communication
EVD_1.Active
Alarm (0=Normal 1=Alarm)
Al_FW_CompatibErr_
EVD Firmware Compability
EVD_1.Active
Alarm (0=Normal 1=Alarm)
Compressor Envelope
Al_HiCurr_COMP_1.
- High Current Alarm
Active
(0=Normal 1=Alarm)
Compressor Envelope -
Al_HiRatioP_COMP_1.
High Pressure Ratio Alarm
Active
(0=Normal 1=Alarm)
Al_HiT_Cond_EVD_1.
Al_HiT_Cond_EVD_1
Active
(0=Normal 1=Alarm)
Al_IncompleteClosing_
EVD Incomplete Closing
EVD_1.Active
Alarm (0=Normal 1=Alarm)
EVD Low Operating
Al_LOP_A_EVD_1.
Pressure Alarm - Valve 1
Active
(0=Normal 1=Alarm)
EVD Low SuperHeat
Al_Low_SH_A_EVD_1.
Alarm - Valve 1 (0=Normal
Active
1=Alarm)
Compressor Envelope -
Al_LowDeltaP_
Low Pressure DeltaAlarm
COMP_1.Active
(0=Normal 1=Alarm)
Compressor Envelope -
Al_LowRatioP_
Low Pressure Ratio Alarm
COMP_1.Active
(0=Normal 1=Alarm)
Low Suction Refrigerant
Al_LowSuct_A_EVD_1.
Temperature - Valve 1
Active
(0=Normal 1=Alarm)
®
Appendix: Points List
ACTIVE
INACTIVE
OBJECT
TEXT
TEXT
INSTANCE
Alarm
Normal
552
Alarm
Normal
553
Alarm
Normal
554
Alarm
Normal
563
Alarm
Normal
564
Alarm
Normal
565
Alarm
Normal
567
Alarm
Normal
576
Alarm
Normal
589
Alarm
Normal
590
Alarm
Normal
591
Alarm
Normal
592
Alarm
Normal
593
Alarm
Normal
594
Alarm
Normal
595
Alarm
Normal
597
Alarm
Normal
598
Alarm
Normal
599
Alarm
Normal
600
Alarm
Normal
601
Alarm
Normal
602
Alarm
Normal
603
Alarm
Normal
604
Alarm
Normal
606
Alarm
Normal
608
Alarm
Normal
609
Alarm
Normal
610
BACNET
OBJECT
ACCESS
HYST
TYPE
ReadCOV_
BV
0
NoWrite
ReadCOV_
BV
0
NoWrite
ReadCOV_
BV
0
NoWrite
ReadCOV_
BV
0
NoWrite
ReadCOV_
BV
0
NoWrite
ReadCOV_
BV
0
NoWrite
ReadCOV_
BV
0
NoWrite
ReadCOV_
BV
0
NoWrite
ReadCOV_
BV
0
NoWrite
ReadCOV_
BV
0
NoWrite
ReadCOV_
BV
0
NoWrite
ReadCOV_
BV
0
NoWrite
ReadCOV_
BV
0
NoWrite
ReadCOV_
BV
0
NoWrite
ReadCOV_
BV
0
NoWrite
ReadCOV_
BV
0
NoWrite
ReadCOV_
BV
0
NoWrite
ReadCOV_
BV
0
NoWrite
ReadCOV_
BV
0
NoWrite
ReadCOV_
BV
0
NoWrite
ReadCOV_
BV
0
NoWrite
ReadCOV_
BV
0
NoWrite
ReadCOV_
BV
0
NoWrite
ReadCOV_
BV
0
NoWrite
ReadCOV_
BV
0
NoWrite
ReadCOV_
BV
0
NoWrite
ReadCOV_
BV
0
NoWrite
Microprocessor Controller for DOAS
MODBUS
REGISTER
INDEX
SIZE
TYPE
10502
Discrete
10503
Discrete
10504
Discrete
10513
Discrete
10514
Discrete
10515
Discrete
10517
Discrete
10526
Discrete
10539
Discrete
10540
Discrete
10541
Discrete
10542
Discrete
10543
Discrete
10544
Discrete
10545
Discrete
10547
Discrete
10548
Discrete
10549
Discrete
10550
Discrete
10551
Discrete
10552
Discrete
10553
Discrete
10554
Discrete
10556
Discrete
10558
Discrete
10559
Discrete
10560
Discrete
49