Greenheck Microprocessor Controller Reference Manual page 44

For dedicated outdoor air system doas v3.001
Table of Contents

Advertisement

VARIABLE
DESCRIPTION
0: Off/Standby
1: Unoccupied Start
2: Occupied Start
5: Dampers Open
6: Fan Start Delay
7: Fans Starting
9: Heat/Cool Delay
10: System On
11: Soft Shutdown
12: System Disabled
13: Remote Off
14: Shutdown Alarm
Unit_Status_Mode
19: Fans Only
20: Economizing
21: Cooling
22: Heating
23: Dehumidifying
25: HGRH Purging
26: Defrost Active
28: Cooling & Heating
29: Dehum w/Heat
30: Overrides Active
31: Expansion Offline
51: IO Test. Sys Disabled
Supply_Temperature_
Active Supply Temperature
Calculated_Setpoint
Setpoint
Cooling_1_Ramp_
Cooling Ramp 1 Status
Capacity
Defrost_Ramp
Defrost Ramp
Economizer_Ramp
Economizer Ramp
Exhaust_Fan_Space_
Exhaust Fan Space Static
Static_Pressure_Ramp
Pressure Ramp
Exhaust_Fan_Supply_
Exhaust Fan Supply
Tracking_Ramp
Tracking Ramp
Head_Pressure_
Head Pressure Control
Control_Ramp_1_
Ramp 1
Ramp
Head_Pressure_
Head Pressure Control
Control_Ramp_2_
Ramp 2
Ramp
Heating_Ramp
Heating Ramp
Hot_Gas_Reheat_
Hot Gas Reheat Ramp
Ramp
Space_CO2_Control_
Space CO2 Control Ramp
Ramp
Supply_Duct_Static_
Supply Duct Static Pressure
Pressure_Ramp
Supply_Fan_Space_
Supply Fan Space Static
Static_Pressure_Ramp
Pressure Ramp
Winter_Ramp_Output
Winter Ramp Output
Outside_Dewpoint
Outside Dewpoint
Outside_Enthalpy
Outside Enthalpy
Space_Dewpoint
Space Dewpoint
Space_Enthalpy
Space Enthalpy
Total_Exhaust_Fan_
Total Exhaust Fan CFM
CFM_BMS
OAD_CFM_BMS
OAD CFM
OAD_Space_Static_
OAD Static Pressure Ramp
Pressure_Ramp
44
Microprocessor Controller for DOAS
Appendix: Points List
ACTIVE
INACTIVE
TEXT
TEXT
Analog Values - Read Only
Value
Ramp
BACNET
OBJECT
OBJECT
ACCESS
INSTANCE
TYPE
ReadCOV_
40
AV
NoWrite
ReadCOV_
41
AV
NoWrite
ReadCOV_
43
AV
NoWrite
ReadCOV_
47
AV
NoWrite
ReadCOV_
48
AV
NoWrite
ReadCOV_
49
AV
NoWrite
ReadCOV_
50
AV
NoWrite
ReadCOV_
51
AV
NoWrite
ReadCOV_
52
AV
NoWrite
ReadCOV_
60
AV
NoWrite
ReadCOV_
61
AV
NoWrite
ReadCOV_
71
AV
NoWrite
ReadCOV_
72
AV
NoWrite
ReadCOV_
74
AV
NoWrite
ReadCOV_
75
AV
NoWrite
ReadCOV_
82
AV
NoWrite
ReadCOV_
83
AV
NoWrite
ReadCOV_
88
AV
NoWrite
ReadCOV_
89
AV
NoWrite
ReadCOV_
107
AV
NoWrite
ReadCOV_
129
AV
NoWrite
ReadCOV_
131
AV
NoWrite
MODBUS
REGISTER
HYST
INDEX
SIZE
TYPE
0
30001
Input
2
0.1
30003
Input
2
1
30007
Input
2
1
30015
Input
2
1
30017
Input
2
1
30019
Input
2
1
30021
Input
2
1
30023
Input
2
1
30025
Input
2
1
30041
Input
2
1
30043
Input
2
1
30063
Input
2
1
30065
Input
2
1
30069
Input
2
1
30071
Input
2
0.1
30085
Input
2
0.1
30087
Input
2
0.1
30097
Input
2
0.1
30099
Input
2
10
30135
Input
2
10
30173
Input
2
1
30177
Input
2
®