6.4

Connecting the cable

Requirement
You require a screwdriver with a maximum blade width of 3.5 mm.
Procedure
1. Strip at least 6 mm of insulation from the load cell cable.
Figure 6-6
2. Insert the stripped load cell cable into the square opening of the screw terminal as far as
it will go.
3. Tighten the screws with the specified tightening torque (Page 33).
Result
The tightened screw firmly holds the stripped wire and establishes the contact.
See also
Design (Page 15)
SIWAREX JB
Operating Instructions, 12/2017, A5E43011851-AA
Strip cable
Connecting
6.4 Connecting the cable
29