Connecting

6.4 Connecting the cable

See also
Internal view (Page 17)
6.4
Connecting the cable
Requirement
You require a screwdriver with a maximum blade width of 3.5 mm.
Procedure
1. In EMC cable glands, lay the cable shielding over a large area.
Figure 6-5
2. With plastic cable glands, place the corresponding wire of the SIWAREX load cell on the shield
terminal.
3. Strip at least 6 mm of insulation from the load cell cable.
Figure 6-6
4. Insert the stripped load cell cable into the square opening of the screw terminal as far as it will
go.
5. Tighten the screws with the specified tightening torque (Page 31).
Result
The tightened screw firmly holds the stripped wire and establishes the contact.
28
Place the cable shield in the EMC cable gland
≥ 6 mm
Strip cable
Operating Instructions, 09/2022, A5E43011851-AD
SIWAREX JB