Carrier Infinity SYSTXCCUID01-V Installation Instructions Manual page 11

Table of Contents

Advertisement

Heater Size:
S (choices dependent upon fan coil model)
This will show the heater size entered during the start- -up process.
This value can be changed to another value (limited by the model
number of the fan coil). If the electric heater is self- -identifying, this
value is not shown.
Elect Heat Lockout
S NONE (default)
S +5 to 55_F (- -15 to 13_C)
Outside temperature above which the electric heat will not operate
except for defrost.
G Terminal
This setup option selects desired operation when the R- -G circuit
changes state on the fan coil control board depending on setup.
S DISABLED (Default)
S FAN - - turns on fan to selected fan speed when G terminal is
energized. See Fig. 26. This setting is used in conjunction with
fresh air supply products (e.g. fresh air make- -up air dampers).
S FAN SPEED - - select Low, Med, High for all zones when G
terminal is energized
S SHUTDOWN - - shuts off fan and equipment when initiated.
This function is not intended for emergency fire shutdown. It
may be activated by a dry contact from an external device such
as a float switch or a relay. User selects whether the contact is
NC - - normally closed (default) or NO - - normally open. User
Interface displays SYSTEM MALFUNCTION on screen and
registers G terminal shutdown event in Last 10 System Events.
See Fig. 27.
Dehum Drain
Turns off the continuous fan at the end of cooling for five minutes
in order to drain the indoor coil of water. The fan will only be
turned off if a dehumidify demand existed at the start of or during
the cooling cycle. Default is enabled.
Reheat Dehum
Enables electric heat to be used while Cool to Dehumidify is
running. This will allow the Cool to Dehumidify function to run
much longer, greatly improving humidity control in cooling mode.
Accumulated
electrical
energy
kilowatt- -hours) is shown on the Fan Coil Run Hours screen and
can be reset there. This is only available with fan coil systems.
Setup - - Heat Pump / AC
Cooling Lockout:
S NONE (default)
S 45_F (7_C)
S 50_F (10_C)
S 55_F (13_C)
Outside temperature below which cooling will not be provided.
Low Ambient Cooling:
S NO (default)
S YES
Selecting YES will enable the low ambient cooling operation in
the outdoor unit. This setting is only available with communicating
outdoor units and with Cooling Lockout set to NONE. Low
ambient kits are not needed with communicating outdoor units.
For detailed sequence of operation, see outdoor unit installation
instructions.
used
while
reheating
(in
Entered Size:
S (dependent on indoor unit model)
Size of the outdoor unit entered during the start- -up process. If the
outdoor unit is a communicating model, this value will not be
shown. This size can be changed here but is limited to sizes that the
indoor unit can handle.
Defrost Interval:
S 30 minutes
S 60 minutes
S 90 minutes
S 120 minutes (default)
S Auto- -Defrost interval optimized by outdoor control (default for
communicating HP)
Time interval at which defrost cycles can occur on a heat pump.
Lockout Temp:
S Off (default)
S +5 to 55_F (- -15 to 18_C)
Locks out the heat pump from operating below the selected outside
temperature. Appears with a fan coil only. Must be below any
electric lockout temperature in Fan Coil Setup.
Quiet Shift
S Off (default)
Turns on
Quiet Shift function
communicating heat pumps.
High Cool Latch:
S NONE (default)
S On
S 80 to 110_F (27 to 43_C)
S DISABLE (disable use of high cool stage)
Outside temperature above which only the high stage (of a 2- -stage
outdoor unit) will run when cooling.
High Heat Latch
S OFF (default)
S On
S 20 to 50_F (- -7 to 10_C) 2 - -stage heat pump runs only high
stage heating below a selectable outdoor temperature. Selections
from 20 to 50_F (- -7 to 10_C) are available in 5_F (3_C)
increments.
S DISABLE (disable use of high heat stage)
Max Heat RPM (Appears with variable capacity heat pump)
Clamps the operating speed of the heat pump to this maximum.
Used to reduce operating noise while in high heating capacity.
Reducing this value will reduce the heating capacity of the heat
pump.
Heat Pump Airflow (Capacity) Limiting
The following settings allow the installer to restrict the heat pump
within certain minimum and maximum airflows. These airflows are
converted to capacities. The Min and Max limits are determined by
the equipment size.
Min CFM (only appears with variable capacity heat pump)
Minimum CFM to run a variable capacity heat pump. This will
increase the minimum operating capacity of the heat pump. Default
value is the heat pump air flow for the lowest heat capacity.
Maximum CFM (only appears with variable capacity heat pump)
Maximum CFM to run a variable capacity heat pump This will
reduce the operating capacity of the heat pump. Default value is the
heat pump air flow for the highest heat capacity.