Toyotomi TAN/TAG-A28EWI Service Manual page 18

Room air conditioner
Table of Contents

Advertisement

TAN/TAG-A28EWI, TAN/TAG-A32EWI
INDICATION LAMP
Micro computer self-diagnose the points of the troubles and inform it by the combination of the status (On, Flush, or
Off) of three lamp indicators on the front panel of the indoor unit.
INDICATION LAMP
ALARM
POWER
TIMER
OPERATION
INDICATION TIME
(green)
(yellow)
(green)
OFF
OFF
OFF
TAN, TAG do not work at all
FLASHING
OFF
OFF
alarm indication appears
FLASHING
ON
ON
immediately when press
ON
ON
FLASHING
operation switch
FLASHING
ON
OFF
OFF
OFF
FLASHING
normal lamp indication
TAN, TAG don't work at all,
turn alarm when
and after 20 sec., operation
lamp is flashing (2 min. in
something is wrong with
case of power on)
TAN, TAG
FLASHING
OFF
FLASHING
OFF
FLASHING
OFF
30 ∼ 40 min. later after
compressor start, the yellow
lamp is flashing and TAN,
TAG stop running
FLASHING
FLASHING
OFF
once stop running with
power lamp lighting when
something is wrong with
TAN, TAG, and start
running again after 3 ∼
20 min.
FLASHING
FLASHING
ON
later after that in case of
or
reoccurrence, alarm
FLASHING
ON
OFF
indication appears
FLASHING
FLASHING
FLASHING
in case of heating operation,
after a few minutes operation,
all lamps are flashing and
TAN, TAG stop running
15 sec. later after main
power on, or 60 sec.
later after start running
FLASHING
ON
FLASHING
through remote controller,
alarm indication appears
40 ∼ 70 sec. later after
start running, alarm
indication appears
OFF
ON
FLASHING
90 sec. later after
start running, alarm
indication appears
-
-
-
-
-
-
-
-
-
-
-
-
※In this table TAN means indoor unit and TAG means outdoor unit.
All manuals and user guides at all-guides.com
APPEARANCE, PORTION, PARTS
SEEMED WRONG
-
-
short or open of sensor,
SENSOR, TEMP. HEAT EXCHANGER
temperature or incomplete
insertion of connector
MIS-WIRING (TAG-TAN CONNECTING
error of transmission
CT disconnection
sensor discharge operate
because temperature of
discharge tube beyond
120°C, or sensor
discharge is bad quality
protective action against
excessive AC current
detection
protective action against
excessive DC current
detection
or
abnormal revolution of
compressor
in case of heating
operation, a rise of
temperature (above 58°C)
SENSOR, TEMP. HEAT EXCHANGER
of RC heat exchanger or
less quantity of RC blow
accident of controller
accident of fan motor
not cool down
-
SENSOR, TEMP. HEAT EXCHANGER
not warm up
water leakage
-
-
nasty smell
louver doesn' t work
-
TROUBLESHOOTING GUIDE
(press the ON/OFF button of remote controller in case of reset)
check the plug inserted into the outlet and the power supply
POWER SUPPLY
emergency operation (display of remote controller is faint or not)
REMOTE CONTROL
check the electric continuity by tester
FUSE(3.15A)
check the electric continuity by tester
TAN TERMINAL BLOCK
PCB (RECEIVER & DISPLAY)
emergency operation
PCB (TAN MAIN)
other than described above
check the resistance by tester [see table 1]
SENSOR, TEMP. ROOM
check the resistance by tester [see table 2]
check the resistance by tester [see table 2]
SENSOR, TEMP. DEFROST
SENSOR, TEMP. DISCHARGE
check the resistance by tester [see table 3]
check the wiring connection and rare contact
CABLE) OR RARE CONTACT
check the electric continuity between 1 and 5 in connector by
tester.[see fig. 1]
CURRENT FUSE . (25A) FUSING
(if it is no continuity, both PCB (TAG main) and power module
(ON THE PCB (TAG MAIN))
should be replaced.)
CUTTING OFF CT
change the PCB (TAG main)
GAS LEAKAGE
check the point of leakage (discharge temperature rise in case of
small leakage), measure the pressure of compressor during fixed
operation (operation frequency 58 Hz)
VALVE, SERVICE IS CLOSED
check the valve by eyes
PIPE
check by eyes
SENSOR, TEMP. DISCHARGE
check the resistance by tester [see table 3]
UNREASONABLE OPERATION
check the place of installation (blockage of air inlet & outlet of TAN,
UNDER OVERLOAD
TAG) check the excessive gas
check the movement by reoperation
MOMENTARY STOP OF POWER
(IN CASE OF LIGHTNING)
DROP OF POWER VOLTAGE
check the power voltage (230V)
UNREASONABLE OPERATION
check the place of installation (blockage of air inlet & outlet of TAN,
UNDER OVERLOAD
TAG) check the excessive gas
MOMENTARY STOP OF POWER
check the movement by reoperation
(IN CASE OF LIGHTNING)
DROP OF POWER VOLTAGE
check the power voltage (230V)
PCB (TAG MAIN)
ACCIDENT OF POWER MODULE
See Flow Chart (P19)
COMPRESSOR LOCKING
FILTER IS CHOKED
check by eyes and clean it
check the resistance by tester [see table 2]
PCB (TAN MAIN)
other than described above
15 sec. later after main power on, if alarm indication appears, PCB
PCB (TAN MAIN)
(TAN main) should be replaced
60 sec. later after start running through remote controller, if alarm
PCB (TAG MAIN)
indication appears, PCB (TAG main) should be replaced
check the current fuse 250V3.15A on the PCB (TAG main) by tester
FAN MOTOR (TAG)
if it is burnt down fan motor (TAG) is defective
if not, fan motor(TAG) or PCB (TAG main) is defective
check the current fuse (1A) on the wiring (red) for fan motor (TAN)
by tester
if the current fuse is cut, fan motor(TAN) is defective
FAN MOTOR (TAN)
if not, fan motor(TAN) or PCB (TAN main) is defective
check the power voltage (230V)
check the voltage of fan motor [see fig.2]
check the point of leakage measure the pressure of compressor
GAS LEAKAGE
during fixed operation (operation frequency 58 Hz)
SENSOR, TEMP. ROOM
check the resistance by tester [see table 1]
check the resistance by tester [see table 2]
4-WAY VALVE
check the resistance by tester [see fig.3]
SHORT CYCLE
check the blockage of air inlet & outlet of TAN, TAG
(INSUFFICIENT AIR CIRCULATION)
DRAINAGE
check the drain hose by eyes (it might be folded or choked)
MIS-INSTALLATION
check the TAN whether lean or not
FILTER IS CHOKED
check by eyes and clean it
NO USE FOR A LONG TIME
NASTY SMELL
use deodorizer
(CIGARETTE, FURNITURE, ETC.)
LOUVER MOTOR
check the resistance by tester [see fig.4]