HEATING MODE OPERATION
The compressor will stop when operational frequency reached the minimum frequency and that condition has
been kept for 6 minutes and the room temperature becomes 4.7℃ higher than it was set.
The compressor will re-start when room temperature becomes 3.7℃ higher than it was set.
The operational frequency will be set every 80 seconds of operation.
The operational frequency setting will be calculated based on the deviation of the room temperature and the
set temperature on one end and the deviation factor at the time of previous setting on another.
Temperature,
indoor heat
exchanger
35˚C
30˚C
15˚C
Super
Indoor fan
Stop
Low
Designated
temperature
+4.7
+3.7
MAX
★1
Frequency of
compressor
0
Hz
All manuals and user guides at all-guides.com
Low
Designate Fan blow
MIN★2
TAN/TAG-A28EWI, TAN/TAG-A32EWI
TAN/TAG-A53EWI
– 14 –
OPERATION DETAILS
Low or Super low
Room temperature
MIN★2
★1
★2
110Hz
24Hz
112Hz
10Hz
Designated Fan blow
MAX
★1