A.O. Smith 100 Series Service Handbook page 66

Commercial boilers/water heaters
Hide thumbs Also See for 100 Series:
Table of Contents

Advertisement

CODE
164
Block intake ON
165
Block intake OFF
166-171
RESERVED
Feedback
172
Main relay feedback incorrect
173
Pilot relay feedback incorrect
174
Safety relay feedback incorrect
175
Safety relay open
176
Main relay ON at safe start check
177
Pilot relay ON at safe start check
178
Safety relay ON at safe start check
179-183
RESERVED
Parameter Faults
184
Invalid BLOWER/HSI output setting
185
Invalid Delta T limit enable setting
186
Invalid Delta T limit response setting
187
Invalid DHW high limit enable setting
188
Invalid DHW high limit response setting
189
Invalid Flame sensor type setting
190
Invalid interrupted air switch enable setting
191
Invalid interrupted air switch start check enable
setting
192
Invalid igniter on during setting
193
Invalid ignite failure delay setting
194
Invalid ignite failure response setting
195
Invalid ignite failure retries setting
196
Invalid ignition source setting
197
Invalid interlock open response setting
198
Invalid interlock start check setting
199
Invalid LCI enable setting
200
Invalid lightoff rate setting
201
Invalid lightoff rate proving setting
202
Invalid Main Flame Establishing Period time
203
Invalid MFEP flame failure response setting
204
Invalid NTC sensor type setting
205
Invalid Outlet high limit response setting
206
Invalid Pilot Flame Establishing Period setting
207
Invalid PII enable setting
208
Invalid pilot test hold setting
209
Invalid Pilot type setting
210
Invalid Postpurge time setting
211
Invalid Power up with lockout setting
66
DESCRIPTION
Servicing should only be performed by a Qualified Service Agent
RECOMMENDED TROUBLESHOOTING OF
LOCKOUT CODES
OEM Specific.
1.
Check wiring and correct any errors.
2.
Inspect the Block Intake Switch to make sure it is
working correctly.
3.
Reset and sequence the module.
4.
During Standby and Purge, measure the voltage
across the switch. Supply voltage should
be present. If not, the Block Intake Switch is
defective and needs replacing.
5.
If the fault persists, replace the relay module.
Internal Fault.
1.
Reset Module.
2.
If fault repeats, replace module.
1.
Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2.
If fault repeats, verify electrical grounding.
3.
If fault repeats, replace module.
1.
Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2.
If fault repeats, verify electrical grounding.
3.
If fault repeats, replace module.
NOTE
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L