A.O. Smith 100 Series Service Handbook page 63

Commercial boilers/water heaters
Hide thumbs Also See for 100 Series:
Table of Contents

Advertisement

CODE
94
Header sensor fault
95
Stack sensor fault
96
Outdoor sensor fault
97
Internal Fault: A2D mismatch
98
Internal Fault: Exceeded VSNSR voltage
99
Internal Fault: Exceeded 28V voltage tolerance
100
Pressure Sensor Fault
101-104
RESERVED
Flame Operation Faults
105
Flame detected out of sequence
106
Flame lost in MFEP
107
Flame lost early in run
108
Flame lost in run
109
Ignition failed
110
Ignition failure occurred
111
Flame current lower than WEAK threshold
112
Pilot test flame timeout
113
Flame circuit timeout
114-116
RESERVED
117
Condensate Fault
118-121
RESERVED
Rate Proving Faults
DESCRIPTION
Servicing should only be performed by a Qualified Service Agent
RECOMMENDED TROUBLESHOOTING OF
LOCKOUT CODES
1.
Check wiring and correct any possible errors.
2.
Replace the header sensor.
3.
If previous steps are correct and fault persists,
replace the module.
1.
Check wiring and correct any possible errors.
2.
Replace the stack sensor.
3.
If previous steps are correct and fault persists,
replace the module.
1.
Check wiring and correct any possible errors.
2.
Replace the outdoor sensor.
3.
If previous steps are correct and fault persists,
replace the module.
Internal Fault.
1.
Reset Module.
2.
If fault repeats, replace module.
1.
Verify the Pressure Sensor is a 4-20ma source.
2.
Check wiring and correct any possible errors.
3.
Test Pressure Sensor for correct operation.
4.
Replace the Pressure sensor.
5.
If previous steps are correct and fault persists,
replace the module.
1.
Check that flame is not present in the combustion
chamber. Correct any errors.
2.
Make sure that the flame detector is wired to the
correct terminal.
3.
Make sure the F & G wires are protected from
stray noise pickup.
4.
Reset and sequence the module, if code
reappears, replace the flame detector.
5.
Reset and sequence the module, if code
reappears, replace the module.
1.
Check pilot valve (Main Valve for DSI) wiring and
operation - correct any errors.
2.
Check the fuel supply.
3.
Check fuel pressure and repeat turndown tests.
4.
Check ignition transformer electrode, flame
detector, flame detector siting or flame rod
position.
5.
If steps 1 through 4 are correct and the fault
persists, replace the module.
Hold time of recycle and hold option. Will not be a
lockout fault. Hold Only.
Internal hardware test. Not a lockout.
Interrupted Pilot or DSI application and flame lost
when system in "test" mode.
1. Reset the module to restart.
Flame sensed during Initiate or off cycle, hold 240
seconds, if present after 240 seconds, lockout.
1.
Check the condensate trap at the back of the
boiler/water heater for any blockage.
2.
Check the exhaust vent piping for any blockage.
NOTE
H
H
H
L
L
L
H
H or L
L
L
L
L
H
H
L
L
L
63