A.O. Smith 100 Series Service Handbook page 62

Commercial boilers/water heaters
Hide thumbs Also See for 100 Series:
Table of Contents

Advertisement

CODE
67
ILK OFF
68
ILK ON
69
Pilot test hold
70
Wait for leakage test completion
71 - 77
RESERVED
78
Demand Lost in Run
79
Outlet high limit
80
DHW high limit
81
Delta T limit
82
Stack limit
83
Delta T exchanger/outlet limit
84
Delta T inlet/exchanger limit
85
Inlet/outlet inversion limit
86
Exchanger/outlet inversion limit
87
Inlet/exchanger inversion limit
88
Outlet T-rise limit
89
Exchanger T-rise limit
90
Heat exchanger high limit
Sensor Faults
91
Inlet sensor fault
92
Outlet sensor fault
93
DHW sensor fault
62
DESCRIPTION
Servicing should only be performed by a Qualified Service Agent
RECOMMENDED TROUBLESHOOTING OF
LOCKOUT CODES
1.
Check wiring and correct any possible shorts.
2.
Check Interlock (ILK) switches to assure proper
function.
3.
Verify voltage through the interlock string to the
interlock input with a voltmeter.
4.
If steps 1-3 are correct and the fault persists,
replace the module.
1.
Verify Run/Test is changed to Run.
2.
Reset Module.
3.
If fault repeats, replace module.
1.
Internal Fault. Reset Module.
2.
If fault repeats, replace module.
1.
Check wiring and correct any possible errors.
2.
If previous steps are correct and fault persists,
replace the module.
1.
Check wiring and correct any possible errors.
2.
Replace the Outlet high limit.
3.
If previous steps are correct and fault persists,
replace the module.
1.
Check wiring and correct any possible errors.
2.
Replace the DHW high limit.
3.
If previous steps are correct and fault persists,
replace the module.
1.
Check Inlet and Outlet sensors and pump circuits
for proper operation.
2.
Recheck the Delta T Limit to confirm proper
setting.
3.
If previous steps are correct and fault persists,
replace the module.
1.
Check wiring and correct any possible errors.
2.
Replace the Stack high limit.
3.
If previous steps are correct and fault persists,
replace the module.
Not Applicable.
Not Applicable.
Not Applicable.
Not Applicable.
Not Applicable.
1.
Check for adequate flow.
Not Applicable.
Not Applicable.
1.
Check wiring and correct any possible errors.
2.
Replace the Inlet sensor.
3.
If previous steps are correct and fault persists,
replace the module.
1.
Check wiring and correct any possible errors.
2.
Replace the Outlet sensor.
3.
If previous steps are correct and fault persists,
replace the module.
1.
Check wiring and correct any possible errors.
2.
Replace the DHW sensor.
3.
If previous steps are correct and fault persists,
replace the module.
NOTE
H or L
H or L
H
H
H
H or L
H or L
H or L
H or L
H or L
H or L
H or L
H or L
H or L
H or L
H or L
H or L
H
H
H