Advertisement

CODE
30
Internal fault: Flame bias shorted to adjacent pin
31
Internal fault: SLO electronics unknown error
32 - 46
Internal fault: Safety Key 0 through 14
System Errors
47
Flame Rod to ground leakage
48
Static flame (not flickering)
49
24VAC voltage low/high
50
Modulation fault
51
Pump fault
52
Motor tachometer fault
53
AC inputs phase reversed
54
Safety GVT model ID does not match application's
model ID
55
Application configuration data block CRC errors
56 - 57
RESERVED
58
Internal fault: HFS shorted to IAS
59
Internal Fault: Mux pin shorted
Normal Event Status
60
Internal Fault: HFS shorted to LFS
61
Anti short cycle
62
Fan speed not proved
63
LCI OFF
64
PII OFF
65
Interrupted Airflow Switch OFF
66
Interrupted Airflow Switch ON
DESCRIPTION
Servicing should only be performed by a Qualified Service Agent
RECOMMENDED TROUBLESHOOTING OF
LOCKOUT CODES
Internal Fault.
1.
Reset Module.
2.
If fault repeats, replace module.
1.
Check the Module and display connections.
2.
Check the Module power supply and make sure
that both frequency, voltage and VA meet the
specifications.
Internal sub-system fault.
1.
Review alert messages for possible trends.
2.
Correct possible problems.
3.
If fault persists, replace module.
1.
Check the Module and display connections.
2.
Check the Module power supply and make
sure that both frequency and voltage meet the
specifications.
3.
On 24Vac applications, assure that J4-10 and
J8-2 are connected together.
Contact the qualified service technician.
Contact the qualified service technician.
Internal Fault.
1.
Reset Module.
2.
If fault repeats, replace module.
Will not be a lockout fault. Hold Only.
1.
Check wiring and correct any faults.
2.
Check Interlocks connected to the LCI to assure
proper function.
3.
Reset and sequence the module; monitor the LCI
status.
4.
If code persists, replace the module.
1.
Check wiring and correct any faults.
2.
Check Preignition Interlock switches to assure
proper functioning.
3.
Check the valve operation.
4.
Reset and sequence the module; monitor the PII
status.
5.
If code persists, replace the module.
1.
Check wiring and correct any possible shorts.
2.
Check airflow switches to assure proper
functioning.
3.
Check the fan/blower operation.
4.
Reset and sequence the module; monitor the
airflow status.
5.
If code persists, replace the module.
NOTE
H
H
L
H
H
H
H
H
H
L
L
L
L
L
L
H
H
H
H or L
H or L
H or L
61