With a Phillips screwdriver, move the end of travel. Fix
it to always keep an opening between 100% and the
minimum desired (50%) in example below.
Sound power levels
Discharge
Measurement conditions:
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
long) fixed to its discharge opening.
Fan
Unit
speed
1
FWD 08
2
3
1
FWD 10
2
3
1
FWD 12
2
3
1
FWD 14
2
3
1
FWD 20
2
3
Intake
Measurement conditions:
Measurements taken at the horizontal air intake.
Fan
Unit
speed
Note for maintenance : Check glycol circuit pressure before free cooling operation season starts. Run glycol pump
1
FWD 08
2
few minutes in manual override during monthly maintenance operation when free cooling is continuously OFF to
3
avoid possible glycol cristalization. Pump Override function is located in TD7 via Button Settings -> Manual Control
1
Settings -> Free Cooling Pump Override.
FWD 10
2
3
1
FWD 12
2
3
1
FWD 14
2
3
1
FWD 20
2
3
RLC-SVX19G-GB
UNT-PRC002-GB
Power level in dB(A), per Hz frequency band
125
250
500
55
50
42
57
54
47
58
57
50
57
51
45
58
54
48
60
58
50
57
51
45
58
54
48
60
58
50
56
62
50
61
66
55
63
69
58
57
63
51
61
66
55
63
69
58
Power level in dB(A), per Hz frequency band
125
250
500
56
55
55
63
62
60
66
65
63
62
58
55
66
63
60
70
67
63
62
58
55
66
63
60
70
67
63
66
65
65
73
72
69
78
76
73
68
72
64
76
76
68
78
79
71
Optional Free-Cooling
1000
2000
37
37
40
30
42
32
42
34
45
38
48
40
42
34
45
38
48
40
48
39
53
47
56
50
49
40
53
47
56
50
If the minimum opening is modified after the first
powering, motor re-calibration is needed to validate the
new operating range. When motor is powered, push
green led button (2). Motor memorizes the new reference
of end of travel position on its signal (2...10 VDC)
1000
2000
53
46
60
53
62
56
58
51
62
56
65
59
58
51
62
56
65
59
65
57
71
64
75
69
64
56
71
65
74
69
Overall power
4000
8000
dB(A)
31
30
46
38
40
50
40
43
53
33
28
48
39
35
51
42
39
54
33
28
48
39
35
51
42
39
54
38
36
56
46
45
60
50
49
63
39
37
57
46
45
60
50
49
63
Overall power
4000
8000
dB(A)
45
42
57
53
53
64
55
57
67
48
44
61
55
52
66
59
57
69
48
44
61
55
52
66
59
57
69
50
46
68
59
57
74
64
63
78
52
50
69
61
61
75
66
66
78
11
137