Installation Environment

2–1

General

2–2

Installation Environment

Noise Prevention
10
This section explains how to install and set up your Control System, with spe-
cifics on the proper environment, actual mounting, applicable cable, wiring,
and switch settings.
Although the K–Type Programmable Controller is quite durable, the following
conditions must be observed in order for your System to operate at its high-
est level of reliability.
Ambient temperature
Humidity
Atmosphere
Vibration and shock
*The ambient operating temperature for the Programming Console is 05 to 455
CAUTION
In low humidity conditions, excessive static electricity of over 8 KV can dam-
age internal components such as ICs. Therefore, before touching the PC, be
sure to first touch a grounded metallic object to discharge any static electric-
ity buildup.
Use twisted pair cables with cross–sectional areas of at least 2 mm
tor (AGW 14) to prevent noise. Avoid mounting the PC close to high–power
equipment, and be sure to mount it at least 200 mm away from power lines.
Wherever possible, use wiring ducts to contain and protect the PC wiring.
The I/O wiring should not be placed in the same duct with the power line or
other wiring. Standard wiring conduits are sufficient as long as the I/O wiring
and power lines are kept separate.
200mm min.
PC
200mm
min.
°
°
Operating: 0
to 55
C*
°
Storage: –20 to 65
C
35% to 85% RH (without condensation)
Must be free from the following:
Corrosive gases
Abrupt temperature changes
Direct sunlight
Concentration of dust, salt, iron particles
Splatter from water, oil, other chemicals
Must not receive direct impact or vibration
Section 2–2
2
/conduc-