Specifications
I/O Link Units
Supply voltage
Operating voltage range
Power consumption
Insulation resistance
Dielectric strength
Noise immunity
Vibration
Shock
Ambient temperature
Humidity
Grounding
Structure
Weight
Dimensions
Relay Service Life (at
Maximum Switching
Capacity)
Transistor and Triac
Specifications
Max. switching capacity
Min. switching capacity
Leakage current
Residual voltage
ON–delay time
OFF–delay time
Do not mix output devices within the same common circuit.
66
100 to 120/200 to 240 VAC 50/60 Hz
85 to 132/ 170 to 264 VAC
15 VA max.
10 M
min. (at 500 VDC) between AC terminals and housing
2,000 VAC 50/60 Hz for 1 minute (between AC terminals and housing)
1,000 V p–p, pulse width: 100 ns to 1
10 to 35 Hz, 2 mm double amplitude, in X, Y, and Z directions, 2 hours each
10 G in X, Y, and Z directions, 3 times each
°
°
Operating: 0
to 55
C
°
°
Storage: –20
to 65
C
35% to 85% RH (without condensation)
Less than 100
IEC IP–30 (mounted in a panel)
1 kg max.
120(w) x 250(h) x 43(d)
Electical
Mechanical
Transistor G3SD–Z01P–PD–US
1 A at 5 to 24 VDC
10 mA at 5 VDC
µ
100
A at 24 VDC
1.5 V max.
1.5 ms max.
1.5 ms max.
µ
s, rise time: 1 ns
300,000 operations [under resistive load (p.f. 1)]
100,000 operations [under inductive load (p.f. 0.4)]
50,000,000 operations
Triac G3S–201PL–PD–US
1 A at 85 to 250 VAC
10 mA at 100 VAC
20 mA at 200 VAC
2 mA at 100 VAC
5 mA at 200 VAC
1.5 V max.
1.5 ms max.
1/2 of load frequency + 1 ms max.