3.48 Inverter Compressor Startup Abnormality

L9
Error Code
Applicable
All outdoor unit models
Models
Method of Error
Detect error according to the signal waveform of compressor.
Detection
Error Decision
When compressor startup operation has not been completed.
Conditions
Supposed
Causes
249
The stop valve is not opened
Defective compressor
Error in wire connections to compressor
Large differential pressure before compressor startup
Defective inverter PCB
SiUS341615E