Blower Motor Hp Mismatch - Daikin RXYQ-TA Series Service Manual

Heat pump 60 hz
Table of Contents

Advertisement

SiUS341615E

3.20 Blower Motor HP Mismatch

C6-01
Error Code
Applicable
FXTQ-TA
Models
Outline
Error is issued if the manufacturer ID and output of the connected fan motor do not match those
recognized by the indoor unit.
Error Decision
Gathers information on the manufacturer ID and output of the fan motor when initializing the fan
Conditions
motor.
If those figures are not the values recognized by the indoor unit, it will be deemed abnormal
operation.
If deemed abnormal operation, it will keep retrying until the figures match.
Error Reset
If the manufacturer ID and output match, the error will be cleared.
Conditions
Supposed
Causes
Corrective
Actions
Service Diagnosis
Incorrect size motor
Indoor unit capacity setting error
Correct motor installation.
Correct the indoor unit capacity setting.