Installing on the S7-1500 standard rail

Installation
1. Place the first housing guide of the device on the top edge of the standard rail
2. Using a screwdriver, pull down the catch
3. Swing the device down while pressing the catch
locks in place.
4. Connect the power supply, refer to the section "Power supply (Page 42)".
5. Fit the connectors for the digital input and digital output, refer to the section "Digital
input/output (Page 45)".
6. Connect the device to the DSL connection, refer to the section "DSL interface (Page 48)".
7. Connect the device to the local network, refer to the section "Ethernet port (Page 49)".
8. Connect the terminal with as short a cable as possible ≤ 150 mm and a large cross-
sectional area of 1.5 mm² to the functional ground of the system, see section "Terminals
(Page 24)" and section "Grounding (Page 44)".
Dismantling
1. Disconnect all connected cables.
2. Using a screwdriver, pull down the catch on the rear of the device.
3. Remove the device from the standard rail.
SCALANCE M812, M816
Operating Instructions, 08/2018, C79000-G8976-C331-06
3.5 Installing on the S7-1500 standard rail
on the rear of the device.
. After it is released, the spring catch
Installation
.
35