Installing On The S7-1500 Standard Rail - Siemens SCALANCE M874 Operating Instructions Manual

Simatic net, industrial remote communication remote networks
Hide thumbs Also See for SCALANCE M874:
Table of Contents

Advertisement

Installation

2.5 Installing on the S7-1500 standard rail

2.5
Installing on the S7-1500 standard rail
Requirement
There is a SIM card for the device.
Installation
1. Insert the SIM card, see section "SIM card (Page 33)".
2. Place the first housing guide of the device on the top edge of the standard rail
3. Using a screwdriver, pull down the catch
4. Swing the device down while pulling down the catch
catch locks in place.
5. Connect the power supply, refer to the section "Power supply (Page 34)".
6. Fit the connectors for the digital input and digital output, refer to the section "Digital
input/output (Page 37)".
7. Connect the antenna, refer to the section "Antennas (Page 39)".
8. Connect the device to the local network, refer to the section "Ethernet port (Page 42)".
9. Connect the terminal with as short a cable as possible ≤ 150 mm and a large cross-
sectional area ≥ 2.5 mm² to the ground of the system, see section "Grounding (Page 36)"
28
on the rear of the device.
. After it is released, the spring
Operating Instructions, 06/2015, C79000-G8976-C331-05
.
SCALANCE M874, M876