Maintenance Normal Maintenance; Filters; Motors; Blower Shaft Bearing - York SUNLINE 2000 Installation Manual

Single package heat pump
Hide thumbs Also See for SUNLINE 2000:
Table of Contents

Advertisement

175245-YIM-C-1008
TABLE 21: HEAT DELAY
Heat
Heat
Red
Fan On
Fan Off
LED 8
Delay
Delay
60
180
60
90
60
60
60
30
45
180
45
90
45
60
45
30
30
180
30
90
30
60
30
30
0
60
0
30
0
10
Non-std
Non-std
MAINTENANCE
NORMAL MAINTENANCE
Prior to any of the following maintenance pro-
cedures, shut off all electric power to the unit to
prevent personal injury.

FILTERS

Inspect once a month. Replace disposable or clean
permanent type as necessary. DO NOT replace per-
manent type with disposable. The dimensional size of
the replacement filter must be the same as the
replaced filter.

MOTORS

Outdoor fan motors are permanently lubricated and
require no maintenance.
Indoor Blower Motor and Drive - The indoor blower
motor features ball bearings that do not require
periodic lubrication. Periodic lubrication of the motor
and bearings can extend the life of components but is
optional.
38
Red
Red
LED 4
LED 2
On
On
On
On
On
On
On
On
Off
On
On
Off
On
Off
On
On
Off
On
On
Off
Off
On
Off
Off
Off
On
On
Off
On
On
Off
On
Off
Off
On
Off
Off
Off
On
Off
Off
On
Off
Off
Off
Off
Off
Off
Red
LED 1
Damage can occur if the bearings are overlu-
On
bricated. Use grease sparingly.
Off
On
Off
On
Off
On
Perform all maintenance operations on the
Off
blower motor with electric power disconnected
On
from the unit. Do not attempt to lubricate bear-
Off
ings with the unit in operation.
On
Off
On an annual basis, check the motor for accumulations
On
of dust, etc. that may block the cooling slots in the
Off
motor shell. Check for loose, damaged or misaligned
On
Off
drive components. Check that all mounting bolts are
tight. Replace defective parts as required.
If desired, every three years remove both pipe plugs at
each end shell and clean out any hardened grease or
foreign matter. Replace one plug on each end with a
clean grease fitting. Using a low pressure grease gun,
pump grease (Chevron SRI-2 or equivalent) into the
bearing cavity until new grease shows at the open port.
Do not over lubricate. Run the motor for ten minutes
until excess grease is purged from the cavity. Replace
the plugs.

BLOWER SHAFT BEARING

Blower shaft bearings should be inspected on a
monthly basis. At a minimum, the bearings should be
relubricated every 6 months using a lithium-based
grease (NLGI grade 2) recommended for ball bearing
service.

OUTDOOR COIL

Dirt should not be allowed to accumulate on the out-
door coil surface or other parts in the air circuit. Clean-
ing should be as often as necessary to keep coil clean.
Use a brush, vacuum cleaner attachment, or other suit-
able means. If water is used to clean coil, be sure elec-
tric power to the unit is shut off prior to cleaning.
Exercise care when cleaning the coil so that
NOTE:
the coil fins are not damaged.