Outdoor Air Thermistor; Electronic Air Cleaner Connections; Humidifier Connections; System Shutdown Accessories - Carrier GC Series Installation Instructions Manual

Geothermal heat pump sizes 024, 036, 048, 060, 072
Table of Contents

Advertisement

Fig. 20 - - OAT Sensor Connection

Outdoor Air Thermistor

A 2- -screw terminal strip is provided for connection of an outdoor
temperature thermistor. The installation of an outdoor temperature
sensor using the ECM board terminals is optional. OAT input can
be used to supply outdoor temperature data for system level
functions and for temperature display on User Interface. If an OAT
is added, it will be used for system level functions.
Using two wires of field- -supplied thermostat wire cable, wire one
lead of thermistor to one screw terminal and the other lead to
remaining screw terminal; there is no polarity to be observed. It is
strongly recommended that two wires be used to connect the
thermistor to eliminate noise interference in temperature reading. If
there are not two spare wires available in cable, one wire may be
used to connect thermistor to OAT screw terminal 1 and the other
lead of the thermistor can be wired to 24VAC COM (C) wire. OAT
screw terminal 1 is terminal located closest to the ABCD system
communications and is marked with a small number 1 next to the
terminal strip.
NOTE: Mis- -wiring OAT inputs will not cause damage to either
ECM board or thermistor. If the thermistor is wired incorrectly, no
reading will appear at User Interface. Re- -wire thermistor correctly
for normal operation.

Electronic Air Cleaner Connections

When using an electronic air cleaner, use airflow sensor part no.
KEAAC0101AAA. The airflow sensor turns on electronic air
cleaner when blower is operating.

Humidifier Connections

The ECM board terminal marked "HUM" is provided for low
voltage (24VAC) control of a humidifier. No humidistat is required
as User Interface monitors indoor humidity. When commanded to
operate humidifier, the ECM board will energize the "HUM"
output to turn humidifier on and de- -energize HUM output to turn
humidifier off. Wire "HUM" and "C" terminals directly to
humidifier as shown in Fig. 18 or 19.

System Shutdown Accessories

The G thermostat terminal input can be configured through the
User Interface to recognize accessories that will shut the system
down in response to a malfunction. The ECM board can be
configured to recognize either Normally Open or Normally Closed
(default) contact devices through the User Interface Set- -Up
screens. Wire the accessory device contacts in series with the R and
Unit Size
Compressor
GC024
ZPS20K5E ---PFV
GC036
ZPS30K5E ---PFV
GC048
ZPS40K5E ---PFV
GC060
ZPS51K5E ---PFV
GC072
ZPS60K5E ---PFV
A150195
Table 7 – Recommended Hard Start Kits
Hard Start Kit
Start Cap
KSAHS2501AAA
HC95DE088
KSAHS2501AAA
HC95DE088
KSAHS2801AAA
HC95DE088
KSAHS2801AAA
HC95DE088
N/A
N/A
G thermostat connections at the ECM board board. The User
Interface will respond to the accessory device signal by ordering a
shutdown
of
the
system
MALFUNCTION on its screen. Refer to the User Interface
Installation Instructions for more detail. See Fig. 21.

Generator

The ECM board G thermostat terminal input can be configured
through the User Interface to recognize a Generator Normally
Open dry- -contact output to signal the system that a generator
malfunction condition exists. Wire the generator output in series
with the R and G thermostat connections at the ECM board. The
User Interface will display GENERATOR MALFUNCTION when
the G thermostat input is energized. This function requires the
addition of a Generator Self Test Verifier (Part No. GSV200) which
must be purchased separately. Visit www.GeneratorVerifier.com for
details and ordering information. Refer to the User Interface
Installation Instructions for more detail. See Fig. 21.

Ventilation Accessory

The G thermostat terminal input can be configured through the
User Interface to recognize a Normally Open dry- -contact output to
signal the system that a Ventilation Accessory requires blower
operation. Blower operation can be configured for Low, Med or
High speed when the G terminal is energized. Wire the Accessory
output in series with the R and G thermostat connections at the
ECM board. Refer to the User Interface Installation Instructions for
more detail. See Fig. 21.
CLS
OPN
COM
Fig. 21 - - "G" Terminal Accessory Wiring

Compressor Start Accessories

In the event of the rare occurrence of compressor starting issues
such as dimming of the residential lights.
voltage issues and add hard start components. Table 7 lists Hard
Start components that are recommended in areas of poor power
conditions.
Start MFD
Start Cap Volts
88 ---108
88 ---108
88 ---108
88 ---108
43
17
and
will
display
SYSTEM
System
System
Shutdown
Shutdown
Device
Device
or
Generator
or
VentilationAccessory
A07121
Verify and correct
Start Relay
330
HN61HB540
330
HN61HB540
330
HN61HB553
330
HN61HB553
330
HN61HB553

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents