American Water Heater 300 Series Instruction Manual page 9

Commercial gas water heaters, power vent/power direct vent gas with direct spark ignition
Table of Contents

Advertisement

* The manifold pressure is the factory setting and is not adjustable. A negative pressure will be seen with just the blower running without
the Gas Control Valve open.
All models - Maximum Supply Pressure: 14 inches W.C. (3.48kPa)
Minimum Supply Pressure for Natural Gas: 3.50" (.87kPa)
Minimum Supply Pressure for Propane Gas: 8.00" (1.99kPa)
Minimum pressure must be maintained under both load and no load (dynamic and static) conditions.
Input
Rating
Rating
(Btu/hr)
(kW)
100,000
29.3
Recovery capacity based on 96% thermal efficiency.
DIMENSIONS AND CAPACITY DATA
Table 2 – CAPACITY, GAS AND ELECTRICAL CHARACTERISTICS
Approximate Capacity
U.S. Gals.
Liters
Gas Type
50
189
75
284
Table 3 – RECOVERY CAPACITIES
F
30
40
Temp.
Rise
C
17
22
GPH
387
291
LPH
1465
1102
*Manifold Pressure
Electrical Characteristics
"WC
kPA
Volts/Hz
Nat./LP
0
0
120/60
Nat/LP
0
0
120/60
Recovery Capacities
50
60
70
80
28
33
39
44
233
194
166
145
882
734
628
549
9
Amperes
<5
<5
90
100
110
120
50
56
61
67
129
116
106
97
488
439
401
367
130
140
72
78
90
83
341
314