FAULT AND ALERT MESSAGES (CONT)
Call the technical support phone number listed on the back cover for further technical assistance or to locate a qualified service technician
in your area.
Possible Causes - Check/Repair
• If Blocked Intake error occurs before blower runs, make sure
pressure switch connections are clean and tight. Check pressure
switch continuity/resistance. Switch should be closed (continuity/0
ohms). Replace switch if open (no continuity).
• If Blocked Intake error occurs when blower is running, check for
restrictions in intake pipe, including intake air connection, outside
termination, and inlet condensate drains (if installed).
• Other possible causes: High wind conditions, excessive negative
air pressure in building.
• Ensure wire connections to the temperature probe are clean and
tight.
• Using a thermometer, check the water temperature of the heater.
• Use a multi-meter and check for continuity between the two red
wires of the temperature probe.
• If the two red wires are open (no continuity) and water temperature
is below 160°F, replace the temperature probe.
• If the water temperature exceeds 195°F, turn off electric power and
gas supply and call Tech Support for further instructions.
• Confirm the water heater is full of water.
• Confirm the powered anode wire connections are tight and free of
debris or moisture (i.e. rust, solder, metal pipe shavings).
• Confirm proper electrical ground to the water heater.
• Inspect powered anode, clean/replace as needed.
NOTE: This Fault only applies to models with powered (non-
sacrificial) anodes.
• Confirm the anode rod is not bent and shorting to the tank.
• Confirm the powered anode is free of contamination between the
anode top and surrounding metal (i.e. solder, loctite, WD40).
• Confirm proper electrical ground to the water heater.
• Inspect powered anode, clean/replace as needed.
NOTE: This Fault only applies to models with powered (non-
sacrificial) anodes.
Displayed Fault/Alert Message
Blocked Air Intake
0 days 0 hrs 0 mins ago
Error Code: A7-1201
Restriction in air intake.
Check intake pipe and
termination for blockage.
Press the Advanced button for
High Temp Limit Exceeded
0 days 0 hrs 0 mins ago
Error Code: A5 - 401
Energy Cut Off has shut off
water heater due to high tank
temperature.
Press the Advanced button for
No Water
0 days 0 hrs 0 mins ago
Error Code: D6 -8
No water detected by Powered
Anode.
The control indicates a problem
with the anode protection. By
ACCEPT
Anode Shorted
0 days 0 hrs 0 mins ago
Error Code: CC -B
The Powered Anode is shorted to
earth ground or the tank.
The control indicates a problem
with the anode
60
BACK
ADVANCED
BACK
ADVANCED
BACK
ADVANCED
BACK
ADVANCED