LOW PROFILE TERMINATION INSTALLATION

This water heater is certified for sidewall direct venting with IPEX
System 636 Low Profile Vent Kit. Follow instructions below for proper
installations.
All termination kits must be located and installed in accordance with
local codes or the current editions of the National Fuel Gas Code
(ANSI Z223.1/NFPA 54) or the Natural Gas and Propane Installation
Code (CAN/CSA B149.1).
1. Once the proper location has been determined, cut 2 holes in the
wall large enough to accomodate the pipe. Pipe diameters and
distance between hole centers can be found in Table 9.
2. Slide both the intake and exhaust pipes through the holes. Solvent
cement both pipes to the base of the vent termination kit, follow the
solvent cementing procedures outlined in the IPEX System 636
Installation Guide, which is available on the web www.ipexinc.com.
3. To fasten the Base to the wall, use the supplied screws and anchors.
A 3/16" (5mm) hole, 1-3/16" (30mm) deep, will need to be drilled for
the anchors. Locate the anchor hole using the base as a template.
4. Screw the Cap to the Base using the supplied screws.
5. Once the vent termination and pipes are secured, the wall
penetrations will need to be sealed from the interior using a PVC-
compatible sealant material.
6. All vent pipes and air inlets must terminate at the same height to
avoid possibility of severe personal injury, death, or substantial
property damage.
8. Operate heater through 1 heat cycle to ensure combustion-air and
vent pipes are properly connected to concentric vent termination
connections.
Air Piping
Vent Piping
Vent Base
Vent Cap
Figure 34
Low Profile Termination Kits - Dimensions
AOS Kit
IPEX Part
Number
Number
100187903
196984
2" Flush Mount Vent Kit
100187887
196985
3" Flush Mount Vent Kit
Qty
1
1
8
4
From Boiler Vent
Pipe Connection
Possible Orientations
Vent
Table 9
Pipe Outside
Description
Diameter
2.375"
3.5"
Table 10
Each Kit Contains
Item Description
Base (two holes)
Cap (one hole)
Stainless Steek Screws
Plastic Anchors
36
To Boiler Intake
Air Connection
Vent/Air
Termination
Grade or
Snow Line
Figure 35
12" Min between Edge of Air
Inlet and Adjacent Vent Outlet
Air
Vent/Air
Termination
Figure 36
Hole Spacing
(ctr to ctr)
5.6"
5.6"
12"
Min to
Over-
Hang
12"
Min