Speed Heat Pump With Single Or Two-Stage Heating (Options For Emergency Heat) With Conventional Two-Stage Thermostat - Goodman MBE Series Installation Instructions Manual

Blower cabinet
Hide thumbs Also See for MBE Series:
Table of Contents

Advertisement

WARNING
NOTES:
1.) Y ENABLES HI SPD FAN COOLING
2.) E ENABLES LO SPD FAN HEATING
W2 AND OT2 CLOSED ENABLES HI SPD FAN HEATING
3.) OT1 PJ4 AND OT2 PJ2 MUST BE CUT
FOR THIS CONFIGURATION
4.) CUT HUM PJ6 JUMPER IF USING HUMIDISTAT
STAT OPENS ON HUMIDITY RISE
5.) DIP SWITCH #4 MUST BE IN THE "ON" POSITION
HEATPUMP - 2 STG EMHT 1 STG AUX - 1 OUTDOOR T'STAT
2 SPEED HEAT PUMP WITH SINGLE OR TWO-STAGE HEATING
(OPTIONS FOR EMERGENCY HEAT) WITH CONVENTIONAL TWO-STAGE THERMOSTAT
NOTES:
1.) Y ENABLES HI SPD FAN COOLING
2.) E ENABLES LOW SPD FAN HEATING
3.) IF OT2 PJ2 JUMBER IS CUT "E' AND "W2"
ENABLE LOW SPD FAN HEATING
4.) CUT HUM PJ6 JUMPER IF USING HUMIDISTAT
STAT OPENS ON HUMIDITY RISE
5.) DIP SWITCH #4 MUST BE IN THE "OFF" POSITION
HEATPUMP - WITH 1 STG EMHT 1 STG AUX HEAT
Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring.
HIGH VOLTAGE!
MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO
MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
OUTDOOR
THERMOSTAT
W2
HEATPUMP
COM
W2
E\W1
W/W2
COM
W2
HEATPUMP
COM
W2
E\W1
DISCONNECT ALL POWER BEFORE SERVICING.
ROOM
THERMOSTAT
W2
THERMOSTATS
OTC
OT1
OT2
Y/Y2
O
OUTDOOR
HEATPUMP
W2
W1
W2
24 VAC
W1
W2
OT1
PJ4
OT2
PJ2
HUM
PJ6
DI
P
PN. B1368274
GOODMAN MFG. CO. L.P.
2nd STAGE HEATER
1ST STAGE HEATER
Figure 27
ROOM
THERMOSTAT
W2
THERMOSTATS
W/W2
O
OTC
OT1
OT2
Y/Y2
OUTDOOR
HEATPUMP
W2
COM
W1
W2
24 VAC
W1
W2
OT1
PJ4
OT2
PJ2
HUM
PJ6
DI
P
PN. B1368274
GOODMAN MFG. CO. L.P.
2nd STAGE HEATER
1st STAGE HEATER
Figure 28
17
HUMIDISTAT
(OPTIONAL)
SEE NOTE 4
HUMIDISTAT
HUM
REMOVE
PRODUCTION
WIRE Y1-O
HUMIDISTAT
(OPTIONAL)
SEE NOTE 4
HUMIDISTAT
REMOVE
HUM
PRODUCTION
WIRE Y1-O