Module 9105 Transmit binary data through data interface

You must first assign the interface to the PLC and initialize it with Module
9100.
Module 9105 transmits a block of binary values from the word memory of the
PLC to one of the two interfaces. The transfer is in the form of ASCII-coded
hexadecimal values. Every byte in the source block makes two ASCII
characters at the interface.
Can only be called in a submit job or spawn job!
Call:
PS
B/W/D/K <>Interface>
0: RS232
1: RS422
PS
K/B/W/D <>Number of the first byte in the binary block>
PS
K/B/W/D <>Length of the binary block (0 to 63)>
CM
9105
Error code:
Marker
Value
Meaning
M4203
0
Data was transmitted
1
Error code in W1022
W1022
1
Incorrect interface or incorrect byte number or block
too long
4
Block outside value range
13
Interface not ready or no connection
14
Interface not assigned
15
Transmit buffer not empty
20
Module was not called in a spawn or submit job
HEIDENHAIN Technical Manual iTNC 530 HSCI