Gas Connections - Raypak 106 User's Installation And Operation Manual

Atmospheric above-ground pool & spa heater
Table of Contents

Advertisement

8' (2.4 m)
OR LESS
24" MIN
(610 mm)
VENT PIPE
DRAFTHOOD
Figure 8.
Vent Piping Requirements
The weight of the vent stack or chimney must not rest on
heater drafthood. Support must be provided in compliance
with applicable codes. The heater top and drafthood must
be readily removable for maintenance and inspection.
Vent pipe should be adequately supported to maintain
proper clearances from combustible construction.
Type "B" double-wall or equivalent vent pipe is
recommended. However single-wall metal vent pipe may
be used as specified in the latest edition of the National
Flue Gas Code ANSI Z223.1 (Canada - CAN/CSA-B149).

4.7. Gas Connections

Gas piping must have a sediment trap ahead of the heater
gas controls, and a manual shut-off valve located outside
the heater jacket. Use the pipe finish flange to seal
between the gas line and the heater jacket. See  Figure
9. All gas piping should be tested after installation in
accordance with local codes.
CAUTION: Do not use 5, 10 or 20 gallon (19.38 to 76
A
Liter) propane tanks, like those used with consumer
barbecues, to supply gas to this heater.
CAUTION: The heater and its manual shut-off valve
A
must be disconnected from the gas supply during any
pressure testing of that system at test pressures in excess
of 1/2 psig (3.5 kPa). The heater and its gas connections
shall be leak tested before placing the appliance in
operation. Use soapy water for leak test. Do not use open
flame.
12
VENT CAP
24" MIN
(610 mm)
HEATER
GAS INLET
5' (1.5 m)
MIN
Figure 9.
Gas Line Sediment Trap
CAUTION: Only sealant tape or a pipe compound rated
A
for use with natural and propane gases is recommended.
Apply sparingly only on male pipe ends, leaving the two
end threads bare.
4.7.1.
Gas Pressure Regulator
The gas pressure regulator is preset at 4" W.C. (1.0kPa) for
natural gas and 10" W.C. (2.5kPa) for propane gas.
If adjustment is needed, remove plug and turn adjustment
screw clockwise to increase pressure or counter-
clockwise to decrease pressure.
Gas Pressure*
Max. Inlet
(Static)
Min. Inlet
(Dynamic)
Manifold Gas
(Dynamic)
*Static means without heater operating. Dynamic refers to heater
operating.
Table G.
Static and Dynamic Gas Pressure
4.7.2.
Gas Pressure Adjustment Location
Figure 10. Honeywell Gas Valve
HEATER JACKET
MANUAL SHUT-OFF VALVE
(Field supplied)
GAS VALVE
FINISH FLANGE
UNION
(Field supplied)
SEDIMENT TRAP
(Field supplied)
Natural Gas
10.5" WC
(2.6 kPa)
5" WC
(1.2 kPa)
4" WC
(1.0 kPa)
Propane Gas
13" WC
(3.2 kPa)
11" WC
(2.7 kPa)
10" WC
(2.5 kPa)