Technical data
6.2 Output
Constant overload current for a
short circuit when powering up,
typical
Short-time overload current for
a short circuit during operation,
typical
Duration of the overcurrent
overload capability for a short
circuit during operation
Remark
•
Can be connected in parallel to
increase the power rating
Remark
•
Number of devices that can be
connected in parallel to
increase the power rating,
quantity
Output characteristic
Figure 6-2
40
6EP1333-3BA10
6EP1334-3BA10
(24 V/5 A)
(24 V/10 A)
6 A
12 A
15 A
30 A
25 ms
25 ms
Every 1 min
Every 1 min
Yes
Switchable characteristic curve with switch A (see Status displays
and signaling (Page 13))
2
See Figure 6-3
See Figure 6-4
6EP1333-3BA10
6EP1334-3BA10
single operation
single operation
output characteristic
output characteristic
(Page 41)
(Page 41)
Startup delay/voltage rise
6EP1336-3BA00
(24 V/20 A)
23 A
60 A
25 ms
Every 1 min
See Figure 6-5
6EP1336-3BA00
single operation
output characteristic
(Page 41)
Operating Instructions, 06.2014, C98130-A7548-A1-3-7629
6EP1337-3BA00
(24 V/40 A)
46 A
120 A
25 ms
Every 1 min
See Figure 6-6
6EP1337-3BA00
single operation
output characteristic
(Page 42)
SITOP modular 1ph/2ph