Siemens SITOP series Operating Instructions Manual page 40

Modular 1ph/2ph
Hide thumbs Also See for SITOP series:
Table of Contents

Advertisement

Technical data
6.2 Output
Constant overload current for a
short circuit when powering up,
typical
Short-time overload current for
a short circuit during operation,
typical
Duration of the overcurrent
overload capability for a short
circuit during operation
Remark
Can be connected in parallel to
increase the power rating
Remark
Number of devices that can be
connected in parallel to
increase the power rating,
quantity
Output characteristic
Figure 6-2
40
6EP1333-3BA10
6EP1334-3BA10
(24 V/5 A)
(24 V/10 A)
6 A
12 A
15 A
30 A
25 ms
25 ms
Every 1 min
Every 1 min
Yes
Switchable characteristic curve with switch A (see Status displays
and signaling (Page 13))
2
See Figure 6-3
See Figure 6-4
6EP1333-3BA10
6EP1334-3BA10
single operation
single operation
output characteristic
output characteristic
(Page 41)
(Page 41)
Startup delay/voltage rise
6EP1336-3BA00
(24 V/20 A)
23 A
60 A
25 ms
Every 1 min
See Figure 6-5
6EP1336-3BA00
single operation
output characteristic
(Page 41)
Operating Instructions, 06.2014, C98130-A7548-A1-3-7629
6EP1337-3BA00
(24 V/40 A)
46 A
120 A
25 ms
Every 1 min
See Figure 6-6
6EP1337-3BA00
single operation
output characteristic
(Page 42)
SITOP modular 1ph/2ph

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sitop psu200m 24 v/5 aSitop psu200m 24 v/10 aSitop modular 24 v/20 aSitop psu100m 24 v/40 a

Table of Contents