5.13.2
Enabling or Disabling TripWise with Function Code 65
1. Press the CODE SELECT key on the keypad.
2. Use the arrow keys to bring up code Cd65 in the display.
3. Press the ENTER key. The display will show either "-----", "OFF" or "ON".
If "-----" is displayed, the TripWise function option is not active on the unit. To add this option to the unit,
the equipment owner would need to contact their Regional Carrier Sales Manager.
4. Use the arrow keys to toggle between "ON" and "OFF" and then press ENTER to select the desired option.
5. If "ON" is selected, the display will show "dAYS". This is the expiration time (2 through 365 in 1 day incre-
ments). Use the arrow keys to change the parameter and then press ENTER to confirm.
The expiration interval is the total maximum days allowed between the running of each test. For exam-
ple, if days are set to 30 and the low speed evaporator fan test has not run within those 30 days, the
TripWise expired message will be displayed. If the TripWise expired message is displayed, it is recom-
mended to pre-trip the unit following customer specific guidelines prior to the next trip.
5.13.3
TripWise Status Event
A TripWise status event will be recorded in the DataCorder recorder when the PTI is selected. In the current
DataLINE software release, the event will show the status of the unit.
In DataLINE version 3.2, perform an all data download - select from the drop down menu "TripWise Summary" then
select a date in "User Logged Events".
NOTE
NOTE
Figure 5.4 TripWise Status in DataCorder
Figure 5.5 Generating TripWise Summary Report