Section: Wire the Burner
6.
Run: With a fl ame established and the control
continuing to detect a fl ame, the burner will operate
in the RUN Mode until the load demand is satisfi ed
or a limit opens.
a.
If terminals RC1 and RC2 are jumpered, the
burner operates in the Low-High-Off Mode.
The burner starts at Low, goes to High after the
fl ame stabilization period. Flame is extinguished
when the load is satisfi ed or a limit opens, and
the burner is sent to motor off delay.
b.
If a high/low control has been wired between
terminals RC1 and RC2 the burner starts at
Low and is released to go High after the fl ame
stabilization period. It can repeatedly cycle
between low and high as necessary to meet
load demand until the load is satisfi ed or a limit
opens. The burner is then sent to Motor-off
Delay.
7.
Recycle: If the fl ame is lost while the burner is
fi ring, the control shuts down the burner, enters a
60 second recycle delay, and repeats the ignition
sequence. The control will continue to Recycle each
time the fl ame is lost, until it reaches a pre-set time
allotment. The control will then go into Hard Lockout
instead of recycle. This feature prevents excessive
accumulation of oil in the appliance fi ring chamber.
Figure 12 - GeniSys 7505 Control with Optional Components
Reset Button
with Red Light
Yellow Light
Green Light
Thermostat Terminals
12
8.
Motor-Off Delay: The oil solenoid valve is turned
off and the control delays turning the motor off
for the set motor-off delay time before the control
returns to standby.
9.
Pump Prime: The igniter and motor are on with the
oil solenoid valve energized for 4 minutes. During
Pump Prime mode, the cad cell is disregarded,
allowing the technician to prime the pump without
having to jumper the cad cell.
Figure 11 - Typical Burner Sequence of Operation - 7505
2
Valve-on delay
8
Motor-off delay
Communication Port 2
Communication Port 1
Optional Components:
Contractor's Tool:
Hand-held device for
programming and diagnostics
Display Module:
Permanent device for
programming and diagnostics
Alarm Module:
For adding isolated low voltage
alarm contacts to the base control.
See Alarm Module Instructions for
specifi cations.
1
9
Standby
3
4
Trial for
ignition
5
Ignition carryover
6
7
Run
Wiring
Connections
Cad Cell
Connections
Pump
prime
Lockout
Recycle