Setting in the normal stations

Connect the engineering tool to the CPU module on the normal station and set the parameters. Set the station number 2 and
3 to the same setting.
1.
Set the CPU module and add a module label of the CPU module. The setting method of the CPU module and addition
method of the module label are the same as those of the control station. ( Page 80 Setting in the control station)
2.
Set the CC-Link IE Controller Network-equipped module as follows.
[Navigation window]  [Parameter]  [Module Information]  Right-click  [Add New Module]
3.
Add a module label of the CC-Link IE Controller Network-equipped module. The addition method of the module label is
the same as that of the control station. ( Page 80 Setting in the control station)
4.
Set the items in "Required Settings" as follows. For the station No.3, set "3" to "Station No.".
[Navigation window]  [Parameter]  [Module Information]  [RJ71GP21-SX]  [Required Settings]
7 COMMUNICATION EXAMPLES
7.2 Communication Examples of CC-Link IE Controller Network