Omron KM-N2-FLK User Manual page 82

Power monitor
Table of Contents

Advertisement

6. Detailed settings for communications
6.2 Modbus (continued)
■ Command (06: H'06)
Command frame
Commu
Function
nication
code
address
H'06
H'FF
Fixed
1
1
Response frame
Commu
Function
nication
code
address
H'06
H'FF
Fixed
1
1
• Start writing address
Set "FFFF" as the dedicated address for commands.
• Written data
The written data is 4 places consisting of the command code plus the related information. Commands are as
follows. Specify command codes using hexadecimal numbers.
Instruction code
03(H'03)
04(H'04)
07(H'07)
09(H'09)
82
Start writing
Written data
address
H'FF
Fixed
2
2
Start writing
Written data
address
H'FF
Fixed
2
2
CRC-16
2
CRC-16
2
Related information
00
00
00
00
Instruction details
Resets any active energy values that
can be reset (individual units)
Move to measuring mode
Moving to setting mode
Initialize (any active energy values that
can be reset and setting values)

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents