3. Basic use
3.4 How to read the setting values (continued)
MENU
Circuit
Setting Item
No.
00
Protocol
01
Communication speed
02
Data length
03
Stop bit
04
Parity
05
Transmission wait time
06
VT ratio
Comm
07
Conversion rate
on
CMMN
08
Conversion display units
09
Pulse output units
0A
Automatic LCD off
0B
Warning ON/OFF
0C
Tariff ON/OFF
0D
Change password
90
Software version display
Others
91
All active energy reset
ETC
92
Initialize
52
Main display
Display of options and input values
MODBS / COMPF
1.2K / 2.4K /4.8K
9.6K / 19.2K / 38.4K(bps)
7 / 8
1 / 2
NONE / ODD / EVEN
00 to 99
1.00 to 999.99
0.000 to 99.999
3 places: XXX
Each place: 0 to 9, A to Z, /, -, _
1 / 10 / 100 / 1K / 5K
10K / 50K /100K (Wh)
OFF / 1.0 / 5.0 / 10.0 (minutes)
ON / OFF
ON / OFF
0000 to 9999
V.1.0.0
-----
-----
Sub display
Default
Unit
Value
PRTCL
MODBS
BPS
9.6K
Modbus: 8 (fixed)
LNGTH
8
CompoWay/F: Select between 7 or 8
STOP
1
PRTY
EVEN
WAIT
20
Set the ratio between the primary voltage and
VT-R
1.00
the secondary voltage when voltage using VT
is input
Set the conversion factor by which active
RATE
10.000
energy is multiplied for each circuit
Set the units for the conversion value using
CHAR
CO2
any 3 characters
WH/P
100
DISP
5.0
OFF means alight constantly
Set the output for the warning for voltage
miss-wiring
ALARM
ON
(Output even when pulse output warning is
OFF)
TARIF
ON
Change the password used when making
PASSW
0001
settings.
The main display shows an example when the
KM-N2
---
version is 1.0.0.
0WH
-----
Clear the active energy for all circuits.
Restore the factory defaults.
RESET
-----
All settings and all measured values are
initialized.