Summary of Contents for National Instruments FieldPoint FP-AI-100

  • Page 1 National Instruments FP-AI-100 Manual Get Pricing & Availability at ApexWaves.com Call Today: 1-800-915-6216 Email: sales@apexwaves.com https://www.apexwaves.com/modular-systems/national-instruments/fieldpoint/FP-AI-100...
  • Page 2 ™ FieldPoint Operating Instructions FP-AI-100 and cFP-AI-100 Eight-Channel, 12-Bit Analog Input Modules These operating instructions describe how to install and use the FP-AI-100 and cFP-AI-100 analog input modules (referred to inclusively as the [c]FP-AI-100). For information about configuring and accessing the [c]FP-AI-100 over a network, refer to the user manual for the FieldPoint network module you are using.
  • Page 3 To install the FP-AI-100, refer to Figure 1 and complete the following steps: 1. Slide the terminal base key to either position X (used for any module) or position 1 (used for the FP-AI-100). 2. Align the FP-AI-100 alignment slots with the guide rails on the terminal base.
  • Page 4 The cFP-CB-x connector block provides the same connections. Table 1 lists the terminal assignments for the signals associated with each channel. The terminal assignments are the same for the FP-TB-x terminal bases and the cFP-CB-x connector blocks. © National Instruments Corp. FP-AI-100 and cFP-AI-100...
  • Page 5 Table 1. Terminal Assignments Terminal Numbers Channel Each channel has separate input terminals for voltage (V ) and current (I ) input. Voltage and current inputs are referenced to the COM terminals. If you are using an external supply to power field devices, connect the power supply to the V and C terminals of the terminal base or connector block.
  • Page 6 Figure 4 shows how to connect a voltage source without an external power supply to one channel of the [c]FP-AI-100. [c]FP-AI-100 To Analog Input Circuitry 1.5 MΩ Voltage Input Source – Impedance To Next Channel Figure 4. Voltage Source without External Power Supply © National Instruments Corp. FP-AI-100 and cFP-AI-100...
  • Page 7 Figure 5 shows how to connect a voltage source with an external power supply to one channel of the [c]FP-AI-100. External Power Supply – [c]FP-AI-100 To Analog Powered Input Circuitry Voltage – Transducer 1.5 MΩ Input Impedance To Next Channel Figure 5.
  • Page 8 [c]FP-AI-100. External Power Supply – [c]FP-AI-100 Loop-Powered Current Transducer To Analog Input Circuitry 100 Ω To Next Channel Figure 7. Current Source with External Power Supply © National Instruments Corp. FP-AI-100 and cFP-AI-100...
  • Page 9: Input Ranges

    Input Ranges To prevent inaccurate readings, choose an input range such that the signal you are measuring does not exceed either end of the range. If a channel is not in use, short the positive input to ground and configure the channel for a bipolar input range. Small fluctuations in floating input signals can cause the red Out of Range status LED on the module to light if the channel is configured for a unipolar range.
  • Page 10: Isolation And Safety Guidelines

    The backplane PE ground terminal has the following symbol stamped beside it: . Connect the Working voltage is defined as the signal voltage plus the common-mode voltage. Common-mode voltage is the voltage of the module with respect to ground. © National Instruments Corp. FP-AI-100 and cFP-AI-100...
  • Page 11: Specifications

    backplane PE ground terminal to the system safety ground using 14 AWG (1.6 mm) wire with a ring lug. Use the 5/16 in. panhead screw shipped with the backplane to secure the ring lug to the backplane PE ground terminal. •...
  • Page 12 0.22% ±5 V ±6 V 0.07% 0.22% ±15 V ±18 V 0.07% 0.22% ±30 V ±36 V 0.07% 0.22% Input impedance........ 1.5 MΩ Effective resolution......11.3 bits Signal input bandwidth ..... 170 Hz © National Instruments Corp. FP-AI-100 and cFP-AI-100...
  • Page 13 Current Inputs The following input signal ranges are software selectable by channel. Typical Maximum Offset Error at Offset Error at Current ° ° 15 to 35 –40 to 70 Input Range 12 µΑ 20 µΑ 0–20 mA 12 µΑ 20 µΑ 4–20 mA ±20 mA 23 µΑ...
  • Page 14 Operating vibration, sinusoidal (IEC 60068-2-6)........ 10–500 Hz, 5 g Operating shock (IEC 60068-2-27)......50 g, 3 ms half sine, 18 shocks at 6 orientations; 30 g, 11 ms half sine, 18 shocks at 6 orientations © National Instruments Corp. FP-AI-100 and cFP-AI-100...
  • Page 15 Safety This product is designed to meet the requirements of the following standards of safety for electrical equipment for measurement, control, and laboratory use: • IEC 61010-1, EN 61010-1 • UL 61010-1 • CAN/CSA-C22.2 No. 61010-1 For UL, hazardous locations, and other safety Note certifications, refer to the product label, or visit , search by model number or...
  • Page 16 Compact FieldPoint controller user manual for the dimensions and cabling clearance requirements of the Compact FieldPoint system. 107.19 mm (4.22 in.) 109.5 mm (4.31 in.) 91.44 mm (3.60 in.) Figure 8. FP-AI-100 Mechanical Dimensions © National Instruments Corp. FP-AI-100 and cFP-AI-100...
  • Page 17: Where To Go For Support

    FieldPoint™, National Instruments™, NI™, and ni.com™ are trademarks of National Instruments Corporation. Product and company names mentioned herein are trademarks or trade names of their respective companies. For patents covering National Instruments products, refer to the appropriate location: Help»Patents in your software, the patents.txt file on your CD, or ni.com/patents .