™ FieldPoint Operating Instructions FP-AI-100 and cFP-AI-100 Eight-Channel, 12-Bit Analog Input Modules These operating instructions describe how to install and use the FP-AI-100 and cFP-AI-100 analog input modules (referred to inclusively as the [c]FP-AI-100). For information about configuring and accessing the [c]FP-AI-100 over a network, refer to the user manual for the FieldPoint network module you are using.
Page 3
To install the FP-AI-100, refer to Figure 1 and complete the following steps: 1. Slide the terminal base key to either position X (used for any module) or position 1 (used for the FP-AI-100). 2. Align the FP-AI-100 alignment slots with the guide rails on the terminal base.
Page 5
Table 1. Terminal Assignments Terminal Numbers Channel Each channel has separate input terminals for voltage (V ) and current (I ) input. Voltage and current inputs are referenced to the COM terminals. If you are using an external supply to power field devices, connect the power supply to the V and C terminals of the terminal base or connector block.
Page 7
Figure 5 shows how to connect a voltage source with an external power supply to one channel of the [c]FP-AI-100. External Power Supply – [c]FP-AI-100 To Analog Powered Input Circuitry Voltage – Transducer 1.5 MΩ Input Impedance To Next Channel Figure 5.
Input Ranges To prevent inaccurate readings, choose an input range such that the signal you are measuring does not exceed either end of the range. If a channel is not in use, short the positive input to ground and configure the channel for a bipolar input range. Small fluctuations in floating input signals can cause the red Out of Range status LED on the module to light if the channel is configured for a unipolar range.
backplane PE ground terminal to the system safety ground using 14 AWG (1.6 mm) wire with a ring lug. Use the 5/16 in. panhead screw shipped with the backplane to secure the ring lug to the backplane PE ground terminal. •...
Page 13
Current Inputs The following input signal ranges are software selectable by channel. Typical Maximum Offset Error at Offset Error at Current ° ° 15 to 35 –40 to 70 Input Range 12 µΑ 20 µΑ 0–20 mA 12 µΑ 20 µΑ 4–20 mA ±20 mA 23 µΑ...
Page 15
Safety This product is designed to meet the requirements of the following standards of safety for electrical equipment for measurement, control, and laboratory use: • IEC 61010-1, EN 61010-1 • UL 61010-1 • CAN/CSA-C22.2 No. 61010-1 For UL, hazardous locations, and other safety Note certifications, refer to the product label, or visit , search by model number or...
FieldPoint™, National Instruments™, NI™, and ni.com™ are trademarks of National Instruments Corporation. Product and company names mentioned herein are trademarks or trade names of their respective companies. For patents covering National Instruments products, refer to the appropriate location: Help»Patents in your software, the patents.txt file on your CD, or ni.com/patents .