Advanced Settings - Sensors; 5.3.7 Advanced Settings - Lockouts; Reminders; Dealer Code - Trane 824 Comfort Control Installation Manual

Works with nexia home intelligence
Table of Contents

Advertisement

Installation Guide
5.3.7 Advanced Settings — Lockouts
MENU ITEM
Auxiliary Heat Lockout
Auxiliary Heat Lockout
Compressor Lockout
Compressor Lockout
Defrost Heater Balance Point (W1)
Defrost Heater Balance Point (W1)
Defrost Heater Balance Point (W2)
Defrost Heater Balance Point (W2)
Defrost Heater Balance Point (W3)
Defrost Heater Balance Point (W3)
Compressor Cooling 1st Stage Lockout
Compressor Cooling 1st Stage Lockout
Compressor Heating 1st Stage Lockout
Compressor Heating 1st Stage Lockout
Furnace Heating 1st Stage Lockout
Furnace Heating 1st Stage Lockout
5.4

reminders

5.5

Dealer Code

page 26
OPTIONS [DEFAULT]
[Disable], Enable
32°F - 70°F Degrees [45°]
[Disable], Enable
5°F - 35°F Degrees [30]
[Disable], Enable
40°F - [55°F]
[Disable], Enable
10°F - 50°F [55°F]
[Disable], Enable
[5°F] - 35°F
[Disable], Enable
80°F - [120°F]
[Disable], Enable
0°F - [50°F]
[Disable], Enable
0°F - [50°F]
DESCRIPTION
Enable auxiliary heat lockout (10° minimum separation when enabling
auxiliary heat lockout and compressor heat lockout)
Select an outdoor temperature to prevent auxiliary heat above the selected
outdoor temperature
Enable compressor heat lockout (10° minimum separation when enabling
auxiliary heat lockout and compressor heat lockout)
Select an outdoor temperature to prevent compressor heating below the
selected outdoor temperature
Enable defrost heater balance point for W1, W2 and W3 (only applicable
when indoor heat is electric or hydronic)
Select an outdoor temperature to disallow 1st, 2nd and 3rd stage of indoor
heat during defrost above this temperature
Enable defrost heater balance point for W1 and W2 (only applicable when
indoor heat is electric or hydronic)
Select an outdoor temperature to disallow 2nd and 3rd stage of indoor heat
during defrost above this temperature
Enable defrost heater balance point for W3 only (only applicable when indoor
heat is electric or hydronic)
Select an outdoor temperature to disallow 3rd stage of indoor heat during
defrost above this temperature
Enable compressor cooling 1st stage lockout
Select an outdoor temperature to force the system to 2nd stage compressor
cooling
Enable compressor heating 1st stage lockout
Select an outdoor temperature to force the system to 2nd stage compressor
heating
Enable furnace heating 1st stage lockout
Select an outdoor temperature to force the system to 2nd stage furnace
heating
18-HD72D1-1