5.3.6 Group 6 Airflow Settings
MENU ITEM
Variable Speed Blower On Delay - Cooling
Non Variable Speed Blower On Delay - Cooling
Variable Speed Blower Off Delay - Cooling
Non Variable Speed Blower Off Delay - Cooling
Variable Speed Blower On Delay - Compressor Heating
Non Variable Speed Blower On Delay - Compressor
Heating
Variable Speed Blower Off Delay - Compressor Heating
Non Variable Speed Blower Off Delay - Compressor
Heating
Hydronic Heat Blower On Delay
Hydronic Heat Blower Off Delay
Compressor Low Stage Air Flow% - Compressor Cooling
Compressor Low Stage Air Flow% - Compressor Cooling
Compressor Low Stage Air Flow% - Compressor Heating
Compressor Low Stage Air Flow% - Compressor Heating
18-HD72D1-1
OPTIONS [DEFAULT]
[No Delay],
1 Minute @ 50%; 7.5 Minutes @ 80%,
1 Minute @ 50%; 4 Minutes @ 80%,
7.5 Minutes @ 80%,
4 Minutes @ 80%,
1 Minute @ 50%,
30 Seconds
[No Delay],
15 Seconds, 30 Seconds
[No Delay],
1.5 Minutes @ 100%,
45 Seconds @ 100%,
30 Seconds % 50%,
1.5 Minutes @ 50%,
3 Minutes @ 50%,
30 Seconds @ 35%
[No Delay],
30 Seconds,
60 Seconds,
90 Seconds
[No Delay],
1 Minute @ 50%; 7.5 Minutes @ 80%,
1 Minute @ 50%; 4 Minutes @ 80%,
7.5 Minutes @ 80%,
4 Minutes @ 80%,
1 Minute @ 50%,
30 Seconds
[No Delay],
15 Seconds,
30 Seconds
[No Delay],
1.5 Minutes @ 100%,
45 Seconds @ 100%,
30 Seconds % 50%,
1.5 Minutes @ 50%,
3 Minutes @ 50%,
30 Seconds @ 35%
[No Delay],
30 Seconds,
60 Seconds,
90 Seconds
[No Delay],
30 Seconds,
60 Seconds
[No Delay],
30 Seconds,
60 Seconds,
90 Seconds
35% - 60% [50%]
55% - [80%]
35% - 60% [50%]
55% - [80%]
824 Programmable Comfort Control
DESCRIPTION
Select the blower on delay for cooling operation
Select the blower on delay for cooling operation
Select the blower off delay for cooling operation
Select the blower off delay for cooling operation
Select the blower on delay for compressor
heating operation
Select the blower on delay for compressor
heating operation
Select the blower off delay for compressor
heating operation
Select the blower off delay for compressor
heating operation
Select the blower on delay for hydronic heating
operation
Select the blower off delay for hydronic heating
operation
Select the 1st stage air flow for a two stage/two
compressor unit in cooling mode
Select the 1st stage air flow for a two stage/
single compressor unit in cooling mode
Select the 1st stage air flow for a two stage/two
compressor unit in heating mode
Select the 1st stage air flow for a two stage/
single compressor unit in heating mode
page 25