2.3 BATTERY INSTALLATION

Battery Safety Precautions

Servicing of batteries should be performed or
supervised by personnel knowledgeable of
batteries and the required precautions. Keep
unauthorized personnel away from batteries.
Refer to SECTION 4 - MAINTENANCE for
additional safety precautions regarding
batteries.
When replacing batteries, use the same number
and type of batteries.
CAUTION
Lead-acid batteries contain hazardous
materials. Batteries must be handled,
transported, and recycled or discarded
in accordance with federal, state, and
local regulations. Because lead is a toxic
substance, lead-acid batteries should be
recycled rather than discarded.
Do not dispose of battery or batteries in
a fire. The battery may explode.
Do not open or mutilate the battery or
batteries. Released electrolyte is harmful
to the skin and eyes. It may be toxic.
A battery can present a risk of electrical
shock and high short circuit current.
observed when working
1. Remove watches, rings, or other metal
objects.
Use tools with insulated handles.
2.
rubber gloves and boots.
Wear
Do not lay tools or
4.
of batteries.
Disconnect charging source prior to
5.
connecting or disconnecting battery
terminals.
Determine if battery is inadvertently
6.
grounded. If inadvertently grounded,
remove source of ground. Contact
with any part of a grounded battery
can result in electrical shock. The
likelihood of such shock will be
reduced if such grounds are removed
during installation and maintenance.
vented

2.3.1 Matching Battery Cabinets

1 .
2.
parts on top
metal
Lead-acid batteries can present a risk of
tire because they generate hydrogen gas.
The following procedures should be
followed:
DO NOT SMOIfE
1.
DO NOT cause flame or spark in
2.
battery area.
Discharge static electricity from body
before touching batteries by first
touching a grounded metal surface.
Cabinet Inspection. Remove all panels
and visually inspect the batteries, bus
Exercise caution; voltage is present
within the Battery Cabinet even before
installation. If there are signs of damage,
do not proceed. Call Liebert Customer
Service and Support at l-800-542-2378.
Battery Storage. The batteries used in the
Battery Cabinet have an excellent charge
retaining characteristic. The batteries can
be stored for up to six months without any
appreciable deterioration. Self-discharge
rate of the batteries is approximately 3% per
month when the batteries are stored in
temperatures of 15OC to 25'C (59°F to 77"F).
If the Battery Cabinet is planned to be
stored for longer than six months, contact
action.
Locating. The Battery Cabinet can be
3.
located conveniently in or outside the
computer room. The &c&-access-only design
eliminates side and rear service clearance
requirements. It also features top or bottom
cable entry areas. However, there are
several considerations to locating your new
Battery Cabinet:
Bolt-on Cabinets. 22-inch wide
l
matching battery cabinets are designed as
a bolt-on section to the UPS module
cabinet. They cannot be installed separate
when near batteries.