Liebert 300 series Installation, Operaton & Maintenance Manual page 80

10-1250kva, 60 hz, three phase
Table of Contents

Advertisement

NONE
Displayed when UPS has called a pager. The UPS has no way to verify that
UNKNOWN
the pager service equipment has received the message, and certainly no way
Although less common, this message will also be displayed if the UPS lost
control power at the moment it was transmitting data to another modem.
The UPS cannot perform a dial-out at the moment because the modem is
NOT READY
not ready. Usually this means that a modem presence test was in progress
at the moment a dial-out request occurred. Try the dial-out test again in a
minute or two. When an actual system event causes a dial-out, a NOT
READY state will not be a problem-the UPS will wait until the modem test
is done and then restart the dial-out.
DISABLED
Displayed in the #2 field if Call #2 is set to NEVER.
NO MODEM
The Modem Mode is set correctly, but the modem is either not installed,
installed incorrectly, or defective.
OUT MODE
The Modem Mode is set to OFF or IN, both disable dial-outs.
OFF
NO DIAL
The modem is responding, but reports 110 dial tone found. Check the phone
TONE
line connection.
The phone line is busy. The UPS will retry the number 20 times before
BUSY
giving up.
NO
The UPS is calling a remote modem, but the remote modem is not
CARRIER
DIALING
The modem is dialing and/or waiting for a response.
SENDING
The modem is transmitting the message to either a remote modem or pager
service equipment.
PASSED
The dial-out succeeded: the UPS connected with a remote modem and
transmitted the messaee.
FAILED
The dial-out failed, UPS was unable to connect and has given up.
Last Attempt(s) Messages
I