Additional modules
Hysteresis
Temperature influence (range:
rotation angle 120° or stroke 14 mm)
Climate class
Storage
Transport
Vibration resistance
Harmonic oscillations
(sine) according to IEC 60068-2-6
Bumping according to IEC 60068-
2-29
Torque for cable gland nut made of
Housing protection type
For connecting to circuits with the
following peak values
Effective internal capacitance
Effective internal inductance
Certificates and approvals
CE conformity
Explosion protection
Types of protection
Intrinsic safety "ia"
Intrinsic safety "ic"
Increased safety "ec" / non-
sparking "nA"
Permissible ambient temperature
7.5.7.2
External position detection system C73451-A430-D78 and 6DR4004-1ES
Ambient temperature
Perm. ambient temperature for operation
Degree of protection
1)
Climate class
Storage
Transport
Operation
) Impact energy max. 1 joule.
1
52
Without Ex protection
≤ 0.1 %/10 K (≤ 0.1 %/18 °F) for -20 to +90 °C (-4 to +194 °F)
≤ 0.2%/10 K (≤ 0.2%/18 °F) for -40 to -20 °C (-40 to -4 °F)
1K5, but -40 to +90 °C (-40 to +194 °F)
2K4, but -40 to +90 °C (-40 to +194 °F)
3.5 mm (0.14"), 2 to 27 Hz, 3 cycles/axis
98.1 m/s² (321.84 ft/s²), 27 to 300 Hz, 3 cycles/axis
300 m/s
Plastic
2.5 Nm (1.8 ft lb)
IP68 according to IEC/EN 60529; NEMA 4X / Encl. Type 4X
-
-
-
The applicable directives and applied standards with their revision levels can be
found in the EU declaration of conformity on the Internet.
Ex markings
ATEX/IECEx
Zone 1:
II 2 G Ex ia IIC T6/T4 Gb
Zone 2:
II 3 G Ex ic IIC T6/T4 Gc
Zone 2:
II 3 G Ex ec IIC T6/T4 Gc
T4: -40 ... +90 °C (-40 ... +194 °F)
T6: -40 ... +70 °C (-40 ... +158 °F)
With Ex protection
Ex "ia"
± 0.2 %
According to IEC/EN 60721-3
(984 ft/s
), 6 ms, 4000 shocks/axis
2
2
Metal
4.2 Nm (3.1 ft lb)
U
= 5 V
i
I
= 160 mA
i
P
= 120 mW
i
C
= 180 nF
i
L
= 922 μH
i
FM/CSA
IS, Class I, Divison 1, ABCD
IS, Class I, Zone 1, AEx ib, IIC
-
NI, Class I, Divison 2, ABCD
NI, Class I, Zone 2, AEx ec, IIC
T4: -40 ... +85 °C (-40 ... +185 °F)
T6: -40 ... +70 °C (-40 ... +158 °F)
In hazardous areas, observe the maximum permissible
ambient temperature corresponding to the temperature
class.
-40 ... +90 °C (-40 ... +194 °F)
IP66 to IEC/EN 60529 / NEMA 4X
According to IEC/EN 60721-3
1K5, but -40 ... +90 °C (1K5, but -40 ... +194 °F)
2K4, but -40 ... +90 °C (2K4, but -40 ... +194 °F)
4K3, but -40 ... +90 °C (4K3, but -40 ... +194 °F)
With Ex protection
Ex "ic", "ec", "nA"
Stainless steel
4.2 Nm (3.1 ft lb)
U
= 5 V
i
C
= 180 nF
i
L
= 922 μH
i