Appendix
A.1 Data formats and data records
A.1.12
Data record 94 - Read measured values
Byte
Meaning
Bit
Measured values
0
Phase current I
1
Phase current I
2
Phase current I
3
Reserved = 0
4 ... 5
Remaining motor cooling time
6
Motor heating
0...6
6
Asymmetry ≥ 40%
7
7
Asymmetry
8 ...15
Reserved = 0
16
Output frequency
17 ... 19
Reserved = 0
20
Line frequency
21
Reserved = 0
22 ... 23
Line-to-line voltage U
24 ... 25
Line-to-line voltage U
26 ... 27
Line-to-line voltage U
28 ... 31
Phase current I
32 ... 35
Phase current I
36 ... 39
Phase current I
40 ... 41
Electronics supply voltage
42
Heatsink temperature
43
Contact block heating
44 ... 45
Remaining cooling time of contact block
46 ... 47
Remaining time for tripping of thermal
motor model
48 ... 51
Output power
52 ... 63
Reserved = 0
94
(%)
L1
(%)
L2
(%)
L3
(rms)
L1-L2
(rms)
L2-L3
(rms)
L3-L1
(rms)
L1
(rms)
L2
(rms)
L3
Value range/ [coding]
0 ... 797 % / [0 ... 255]
0 ... 797 % / [0 ... 255]
0 ... 797 % / [0 ... 255]
0 ... 1 800 s / [0 ... 18 000]
0 ... 200 % / [0 ... 100]
No asymmetry [0]
Asymmetry (≥ 40%) [1]
0 ... 100 % / [0 ...100]
0 ... 100 Hz / [0 ... 200]
0 ... 100 Hz / [0 ... 200]
0 ... 1500 V / [0 ... 15000]
0 ... 1500 V / [0 ... 15000]
0 ... 1500 V / [0 ... 15000]
0 ... 20000 A / [0 ... 2000000]
0 ... 20000 A / [0 ... 2000000]
0 ... 20000 A / [0 ... 2000000]
0 ... 1500 V / [0 ... 15000]
-40 ... 127 °C / [-40 ... 127]
0 ... 250 °C / [0 ... 250]
0 ... 1800 s/ [0 ... 18000]
0 ... 10000 s/ [0 ... 10000]
0 ... 2147483 W /
[0 ... 21474830]
PROFINET Communication Module for SIRIUS Soft Starter 3RW44
Manual, 12/2013, A5E31996495002A/RS-AA/001
Increment
Comment
3.125 %
8-bit current format
3.125 %
8-bit current format
3.125 %
8-bit current format
0.1 s
2 %
1 %
0.5 Hz
0.5 Hz
0.1 V
0.1 V
0.1 V
0.01 A
0.01 A
0.01 A
0.1 V
1 °C
1 °C
0.1 s
1 s
0.1 W