Configuring/assigning parameters

5.2 Configuring the properties of 3RW44 PN as IO device

There are two options for assigning parameters for the PROFINET communication module:
● Stand-alone program on PC or programming device with PROFINET connection (point-
to-point)
● Integration with the object manager (OM) in STEP 7
You can find detailed information about "Soft Starter ES" in the online help for the
program.
You can download the "Soft Starter ES 2007" software under Test version
(http://support.automation.siemens.com/WW/view/de/28323168). This is a free, 14-day test
version.
5.1.3

Diagnostics package

A free diagnostics package is available for the 3RW44 soft starters. It contains HMI
diagnostics masks for a touch panel. The diagnostics package is available in German and
English. You can download the diagnostics package
at (http://support.automation.siemens.com/WW/view/de/28557893).
5.2
Configuring the properties of 3RW44 PN as IO device
Assigning the device name and IP parameters for an IO device
PROFINET IO communication requires setting and configuring the IO device name and the
IP parameters.
The device name and the IP parameters can be assigned in different ways:
● Assigning the device name using the configuration tool of the automation system
● Configuring the device name using the "Soft Starter ES 2007" software and transferring it
to the device
● Assigning the device name via the display in the 3RW44 basic device
Assigning the device name using the configuration tool of the automation system
The device name is assigned during the commissioning phase by the configuration tool of
the automation system (e.g., STEP 7) and transferred to the IO device via Ethernet. For the
transfer, the soft starter must be connected and accessible via the Ethernet interface. The
device can be accessed via LAN using the MAC address (e.g., 00-0E-8C-BD-1F-27) printed
on the front of the communication module.
28
PROFINET Communication Module for SIRIUS Soft Starter 3RW44
Manual, 12/2013, A5E31996495002A/RS-AA/001