Appendix; Data Formats And Data Records; Process Data And Process Images; A.1 Data Formats And Data Records - Siemens SIRIUS PROFINET Manual

Industrial controls, communication module for soft starter
Table of Contents

Advertisement

Appendix

A.1

Data formats and data records

A.1.1

Process data and process images

Process image
The process image is a component of the system memory of the CPU. At the start of the
cyclic program, the signal states of the inputs are transferred to the process image of the
inputs. At the end of the cyclic program, the process image of the outputs is transferred to
the IO device as a signal state.
For soft starters with PROFINET, the following process image is available:
● Process image with 2 bytes outputs / 2 bytes inputs (16 O/16 I)
The following table contains the the process data and process images:
Outputs
PROFINET Communication Module for SIRIUS Soft Starter 3RW44
Manual, 12/2013, A5E31996495002A/RS-AA/001
Process data Process image:
(16 O, DO 0.0 to DO 1.7)
(16 I, DI 0.0 to DI 1.7)
DO 0.0
Motor right
DO 0.1
Motor left
DO 0.2
Not assigned
DO 0.3
Trip Reset
DO 0.4
Emergency start
DO 0.5
Not assigned
DO 0.6
Slow speed
DO 0.7
Not assigned
DO 1.0
Output 1
DO 1.1
Output 2
A