Connections
Notes:
•
Verify that all system components are installed in accordance with
instructions.
•
All connections are made to removable screw terminal connectors located
at the rear of the meter.
!
WARNING:
•
Use copper wire with +60 °C or +60/75 °C (+140 °F or +140/167 °F)
insulation for all line voltage connections.
•
Observe all safety regulations.
•
Electrical wiring should be performed in accordance with all
applicable national, state, and local codes to prevent damage to
the meter and ensure personnel safety.
Connector Labeling
The connectors label, affixed to the meter, shows the location of all connectors available
with requested configuration. It also identifies the location of the RTD/TC selector switch.
Connector Labeling for Two Relays and 24 V Supply
Power Connections
Power connections are made to a two-terminal connector labeled POWER on diagram
Connector Labeling for Two Relays and 24 V Supply. The meter will operate regardless of
DC polarity connection. The + and - symbols are only a suggested wiring convention.
7ML19985JS01
power
connector
required external fuse: 5
A max, slow blow
SITRANS RD200 – OPERATING INSTRUCTIONS
AC or DC
power
Page 11