Mitsubishi Electric FX2N-64DP-M Hardware Manual

Profibus-dp master block, melsec-f

Advertisement

Quick Links

HARDWARE MANUAL
FX
-64DP-M Profibus-DP Master Block
2N

Advertisement

Table of Contents
loading

Summary of Contents for Mitsubishi Electric FX2N-64DP-M

  • Page 1 HARDWARE MANUAL -64DP-M Profibus-DP Master Block...
  • Page 2 FX2N-64DP-M Profibus-DP Master Block Foreword • This manual contains text, diagrams and explanations which will guide the reader in the correct installation and operation of the FX -64DP-M Profibus-DP Master Block. It should be read and understood before attempting to install or use the unit.
  • Page 3 FX2N-64DP-M Profibus-DP Master Block -64DP-M Profibus-DP Master Block Manual number : JY992D82901 Manual revision : D Hardware Manual Date : March 2001...
  • Page 4 FX2N-64DP-M Profibus-DP Master Block...
  • Page 5 FX2N-64DP-M Profibus-DP Master Block Guidelines for the Safety of the User and Protection of the FX -64DP-M Profibus-DP Master Block. This manual provides information for the use of the FX -64DP-M Profibus-DP Master Block. The manual has been written to be used by trained and competent personnel. The definition of...
  • Page 6 FX2N-64DP-M Profibus-DP Master Block Note’s on the Symbols Used in this Manual At various times through out this manual certain symbols will be used to highlight points of information which are intended to ensure the users personal safety and protect the integrity of equipment.
  • Page 7 FX2N-64DP-M Profibus-DP Master Block • Under no circumstances will Mitsubishi Electric be liable responsible for any consequential damage that may arise as a result of the installation or use of this equipment. • All examples and diagrams shown in this manual are intended only as an aid to understanding the text, not to guarantee operation.
  • Page 8 FX2N-64DP-M Profibus-DP Master Block...
  • Page 9: Table Of Contents

    FX2N-64DP-M Profibus-DP Master Block Table of Contents Guideline ..................... iii 1. Introduction....................1-1 1.1 Features of the 64DP-M ..................1-1 1.2 External Dimensions and Each Part Name ............1-2 1.2.1 Pin Configuration of Profibus-DP Communication Port ..........1-5 1.3 System Configuration ..................1-6 1.3.1 Applicable Profibus-DP Network ................
  • Page 10 FX2N-64DP-M Profibus-DP Master Block 3. Specifications ..................3-1 3.1 General Specifications..................3-1 3.2 Power Supply Specifications ................3-1 3.3 Performance Specifications ................. 3-2 4. Mode and Displayed Station Address ...........4-1 4.1 Mode........................4-1 4.1.1 Mode Setting Switch....................4-2 4.2 Displayed Station Address .................. 4-3 5.
  • Page 11: Introduction

    FX2N-64DP-M Profibus-DP Master Block Introduction 1 Introduction Features of the 64DP-M The FX -64DP-M Profibus-DP Master Block (hereafter called “64DP-M”) is a “Class 1” master for the Profibus-DP network (hereafter called “Profibus-DP”). The FX series programmable controller by connecting 64DP-M can read input data from the Profibus-DP slave (hereafter called “DP-slave”), and write output data to the DP-slave.
  • Page 12: External Dimensions And Each Part Name

    FX2N-64DP-M Profibus-DP Master Block Introduction 1 External Dimensions and Each Part Name Dimensions: mm (inches) MASS (Weight): Approx. 0.4kg (0.88 lbs) Accessory: Special block No. label Figure 1.1: External Dimensions 8 7 ( 3 . 4 3 " ) 8 5 ( 3 . 3 5 " ) j ) k ) 5 ( 0 .
  • Page 13 FX2N-64DP-M Profibus-DP Master Block Introduction 1 c) RS-232C port (9-pin D-SUB Connector: #4-40unc inch screw thread) The cable connecting between 64DP-M and personal computer is Blue ProfiCab cable. For Blue ProfiCab, refer to MELSEC ProfiMap Configuration System for Open Networks Software Manual.
  • Page 14 FX2N-64DP-M Profibus-DP Master Block Introduction 1 f) TEST LED and STATION LED Table 1.2: TEST LED and STATION LED LED Name Description TEST LED ON when self-diagnosis mode is executing. Displays the station address (Binary) during normal operation. Displays the test STATION type during self-diagnosis mode.
  • Page 15: Pin Configuration Of Profibus-Dp Communication Port

    FX2N-64DP-M Profibus-DP Master Block Introduction 1 1.2.1 Pin Configuration of Profibus-DP Communication Port The connector is a 9-pin D-SUB (#4-40unc inch screw thread) type, the pin configuration is shown below. Figure 1.2: Pin Layout of Profibus-DP Communication Port Table 1.4: Profibus-DP Communication...
  • Page 16: System Configuration

    FX2N-64DP-M Profibus-DP Master Block Introduction 1 System Configuration 1.3.1 Applicable Profibus-DP Network Note; • The maximum number of slaves that can be connected to a 64DP-M is 60. • Number that can be connected for 1 segment ≤ Masters + slaves + repeaters 32 units •...
  • Page 17 FX2N-64DP-M Profibus-DP Master Block Introduction 1 Note; When using a slave with expansion diagnostic information of more than 32 bytes, the network will be limited. Maximum expansion diagnostic information data length is the smaller of the value obtained from a slave address by the following equation or 244 bytes.
  • Page 18 FX2N-64DP-M Profibus-DP Master Block Introduction 1 Figure 1.3: Example System Configuration <Connecting 1 Master (class 1) on the Profibus-DP Network> Configuration -64DP-M Software Series (Master of Class 1) Terminating (ProfiMap) resistor Terminating resistor Profibus-DP Network Slave Slave Slave Slave Slave Slave No.1...
  • Page 19: Applicable Programmable Controller

    FX2N-64DP-M Profibus-DP Master Block Introduction 1 1.3.2 Applicable Programmable Controller For setting up a system, the 64DP-M can be connected directly to the FX series programmable controller’s extension port, or to any other extension unit / block’s right side extension port.
  • Page 20 FX2N-64DP-M Profibus-DP Master Block Introduction 1 MENO 1-10...
  • Page 21: Wiring And Mounting

    FX2N-64DP-M Profibus-DP Master Block Wiring and Mounting 2 Wiring and Mounting Caution 1) Do not lay signal cable near to high voltage power cable or house them in the same trunking duct. Effects of noise or surge induction may occur. Keep signal cables a safe distance of more than 100 mm (3.94") from these power cables.
  • Page 22: Mounting

    FX2N-64DP-M Profibus-DP Master Block Wiring and Mounting 2 Mounting 2.1.1 Arrangements The 64DP-M connects on the right side of an FX series main unit or extension unit/block (including special function blocks). For further information of mounting arrangements, refer to the hardware manual of the associated main unit.
  • Page 23 FX2N-64DP-M Profibus-DP Master Block Wiring and Mounting 2 Figure 2.2: Attach to DIN Rail and Remove from DIN Rail  „ ƒ ‚ 2) Direct mounting to back walls The 64DP-M can be mounted with an M4 screws by using the direct mounting holes.
  • Page 24: Wiring

    FX2N-64DP-M Profibus-DP Master Block Wiring and Mounting 2 Wiring 2.2.1 Wiring of Power Supply The 64DP-M needs power to be supplied from an FX series PLC or external power supply. Caution When the 64DP-M is supplied with 24V DC from external power supply, it needs to be started up at the same time as the FX series PLC.
  • Page 25 FX2N-64DP-M Profibus-DP Master Block Wiring and Mounting 2 Figure 2.3: Power Supply From PLC +24V -24V Series PLC -64DP-M Figure 2.4: Power Supply From External Power Supply External power supply +24V -24V Series PLC -64DP-M...
  • Page 26: Wiring Of Profibus-Dp

    FX2N-64DP-M Profibus-DP Master Block Wiring and Mounting 2 2.2.2 Wiring of Profibus-DP To connect the 64DP-M to a Profibus-DP network use only the Profibus connectors and shielded twisted-pair cable complying with EN50170. For Profibus connectors see the Profibus connector’s manual.
  • Page 27: Terminating Resistor

    FX2N-64DP-M Profibus-DP Master Block Wiring and Mounting 2 Figure 2.6: Profibus Connection Shielded twisted-pair cable of Profibus-DP network -64DP-M Profibus-DP Master Block 2.2.3 Terminating Resistor The units at each end of the Profibus-DP network must have a terminating resistor. This will either be in the master or slave unit or in the Profibus connector.
  • Page 28 FX2N-64DP-M Profibus-DP Master Block Wiring and Mounting 2 MEMO...
  • Page 29: Specifications

    FX2N-64DP-M Profibus-DP Master Block Specifications 3 Specifications General Specifications Table 3.1: General Specifications Items Description General specifications excluding Same as those of the main unit Dielectric Withstand Voltage 500 V AC > 1 min., Dielectric Withstand Voltage tested between DC power supply terminals and earth...
  • Page 30: Performance Specifications

    FX2N-64DP-M Profibus-DP Master Block Specifications 3 Performance Specifications Table 3.3: Performance Specifications Item Specifications Transmission Type Bus network Unit type Profibus-DP master Class 1 Transmission Data ONLINE1(Normal service mode): 32 bytes / slave (Maximum Exchanged Data ONLINE2(Extended service mode): 244 byte/slave...
  • Page 31 FX2N-64DP-M Profibus-DP Master Block Specifications 3 Table 3.3: Performance Specifications Item Specifications PNO ID F264 H Port for download configuration RS-232C (9 pin D-SUB Connector: #4-40unc inch screw thread) Connector Profibus-DP Port for Profibus-DP network Network (9 pin D-SUB Connector: #4-40unc inch screw thread)
  • Page 32 FX2N-64DP-M Profibus-DP Master Block Specifications 3 Table 3.3: Performance Specifications Item Specifications ON when 24V DC power is supplied form the PLC or external power POWER LED supply. ON: During normal operation RUN LED OFF: Error Flashes during communication with slave on the Profibus network.
  • Page 33 FX2N-64DP-M Profibus-DP Master Block Specifications 3 Note 1; When using a slave with expansion diagnostic information of more than 32 bytes, the network will be limited. Maximum expansion diagnostic information data length is the smaller of the value obtained from a slave address by the following equation or 244 bytes.
  • Page 34 FX2N-64DP-M Profibus-DP Master Block Specifications 3 Note 2; Length that the bus can be expanded by using repeaters. × Maximum Bus Length = (“Number of repeaters” + 1) “Bus Length / segment” Table 3.4: Maximum Bus Length and Baud Rate...
  • Page 35: Mode And Displayed Station Address

    FX2N-64DP-M Profibus-DP Master Block Mode and Displayed Station Address 4 Mode and Displayed Station Address Mode The 64DP-M has 4 modes, decided by the mode setting switch. For setting instructions, refer to subsection 4.1.2. Table 4.1: Mode Mode Description ONLINE 1 (Normal service mode) 64DP-M can exchange 32 bytes/slave.
  • Page 36: Mode Setting Switch

    FX2N-64DP-M Profibus-DP Master Block Mode and Displayed Station Address 4 4.1.1 Mode Setting Switch The mode is decided by the mode setting switch. Default setting is “0” (Online 1 mode). Caution When changing the Mode, the power supply of the PLC and 64DP-M should be OFF.
  • Page 37: Displayed Station Address

    FX2N-64DP-M Profibus-DP Master Block Mode and Displayed Station Address 4 Displayed Station Address The station address set by parameter is displayed by the STATION LEDs when 64DP-M is in ONLINE 1 mode. The station address is displayed by the STATION LED (B0-B6) in binary. The parameter is set by configuration software (ProfiMap).
  • Page 38 FX2N-64DP-M Profibus-DP Master Block Mode and Displayed Station Address 4 MEMO...
  • Page 39: Diagnostics

    FX2N-64DP-M Profibus-DP Master Block Diagnostics 5 Diagnostics If the 64DP-M does not see to operate normally, check the following items. Preliminary Checks 1) Check “POWER LED” If “POWER LED” is OFF, check the wiring of the 24V DC power supply, and check whether the 24V DC voltage source capacity is sufficient.
  • Page 40: Check The Status Of The Leds For The 64Dp-M

    FX2N-64DP-M Profibus-DP Master Block Diagnostics 5 Check the Status of the LEDs for the 64DP-M 1) POWER LED check Table 5.1: POWER LED Check State Description The 24V DC power supply (PLC or external power supply) is correctly supplied. Check wiring of power supply, and check whether the 24V DC voltage source capacity Unlit of 24V DC power supply.
  • Page 41 FX2N-64DP-M Profibus-DP Master Block Diagnostics 5 3) SD/RD LED check Table 5.3: SD/RD LED Check State Description If 64DP-M is the exchange start processing or exchange stop processing status, this state of LED is normal operation. However, when 64DP-M exchange to slave(s), check parameter setting of slave in 64DP-M.
  • Page 42 FX2N-64DP-M Profibus-DP Master Block Diagnostics 5 5) RADY LED check Table 5.5: RADY LED Check State Description 64DP-M is in operation mode 0 or E. If it is not in these mode, please contact a service representative. 64DP-M is not operation mode 0 or E. If it is in these mode, please contact a service Unlit representative.
  • Page 43 FX2N-64DP-M Profibus-DP Master Block Diagnostics 5 8) RSP ERR LED check Table 5.8: RSP ERR Check State Description 64DP-M is fault when exchange data to slave. Check diagnostic information. For diagnostic information, refer to section 4.12. Unlit 64DP-M is normal operation.
  • Page 44: Self Diagnostic Of The 64Dp-M

    FX2N-64DP-M Profibus-DP Master Block Diagnostics 5 Self Diagnostic of the 64DP-M When setting the self diagnostic mode (The mode switch in position “2”.), TEST LED and ST NO LED will be lit as shown in the following table. When the test result is normal, these tests are repeated in order of a -e).
  • Page 45 FX2N-64DP-M Profibus-DP Master Block Diagnostics 5 Figure 5.1: LED Location TEST ST NO : LED is not lit. : LED is lit.
  • Page 46 FX2N-64DP-M Profibus-DP Master Block Diagnostics 5 MEMO...
  • Page 47: Further Information Manual List

    FX2N-64DP-M Profibus-DP Master Block Appendix A Appendix A: Further Information Manual List Table A-1: Further Information Manual List Manual name Manual No. Description Series This manual contents expiantions for wiring, Programmable controllers JY992D66301 installation and specification, etc. about FX Series Hardware Manual programmable controller.
  • Page 48 FX2N-64DP-M Profibus-DP Master Block Table A-1: Further Information Manual List Manual name Manual No. Description This manual contents expiantions for wiring, -64DP-M installation, specification and allocation BFM’s, etc. Profibus-DP Master Block JY992D88001 about FX -64DP-M Profibus-DP Master Block. User’s Manual However, this hardware manual’s text is already...
  • Page 49 FX2N-64DP-M Profibus-DP Master Block MEMO...
  • Page 50 FX2N-64DP-M Profibus-DP Master Block MEMO...
  • Page 52 HARDWARE MANUAL -64DP-M Profibus-DP Master Block HEAD OFFICE: MITSUBISHI DENKI BLDG MARUNOUCHI TOKYO 100-8310 TELEX: J24532 CABLE MELCO TOKYO HIMEJI WORKS: 840, CHIYODA CHO, HIMEJI, JAPAN Effective MAR. 2001 JY992D82901D Specification are subject (MEE) to change without notice.

This manual is also suitable for:

Fx2n