2. General Troubleshooting

2.1
Error Display (Indoor Unit)
When the indoor unit encounters a recognized error, an error code will be displayed. These error codes are described in
the following table:
Display
E0/EA
Indoor unit EEPROM parameter error
Indoor / outdoor units communication error
E1
The indoor fan speed is operating outside of the normal range
E3
E4
Indoor room temperature sensor T1 is in open circuit or has short circuited
Evaporator coil temperature sensor T2 is in open circuit or has short circuited
E5
Communication error between the indoor PCB and display board
Eb
EF
Intelligent eye module error
Overload current protection
F0
Outdoor ambient temperature sensor T4 open circuit or short circuit
F1
F2
Condenser coil temperature sensor T3 is in open circuit or has short circuited
Compressor discharge temperature sensor TP open circuit or short circuit
F3
Outdoor unit EEPROM parameter error
F4
F5
The outdoor fan speed is operating outside of the normal range
IPM malfunction or IGBT over-strong current protection
p0
Over voltage or over low voltage protection
p1
High temperature protection of IPM module
p2
p4
Inverter compressor drive error
For other errors:
The display board may show a garbled code or a code undefined by the service manual. Ensure that this code is not a
temperature reading.
Troubleshooting:
Test the unit using the remote control. If the unit does not respond to the remote, the indoor PCB requires replacement.
If the unit responds, the display board requires replacement.
Error Information
Solution
Page 61
Page 62
Page 64
Page 67
Page 67
Page 68
Page 66
Page 69
Page 67
Page 67
Page 67
Page 61
Page 64
Page 70
Page 71
Page 73
Page 74
Page 51

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

38qhp09e8s42qhp12e8s38qhp12e8s

Table of Contents