Generator; Section 1 - General Information; Specifications; Engine - Carrier ASPAX1CCA015 Installation And Owner's Manual

Air-cooled automatic standby generators 13 kw ng, 15 kw lp
Hide thumbs Also See for ASPAX1CCA015:
Table of Contents

Advertisement

" GENERAL °
NFORMATON
Section 1 - General information
1S kW Generator
1.6
1.6.1
GENERATOR
Rated Maw Cont
Power Capacity
(Watts _) ..... 13,000 NG/
15,000 LP+
Rated Voltage .......................................................
120/240
Rated Max. Conthmous
Load Current (Amps)
120 Volts + ......................................
108.3
NG/125_0
LP
240 VoRs ............................................
54.2 NG/62.5
LP
Main Line Circuit
Breaker
....................................
65 Atnp
Phase
.............................................................................
1
Nmnber
of Rotor
Poles ...................................................
2
Rated AC Frequency
................................................
60 Hz
Power
Factor
..................................................................
1
Recommended
Air Filter ...........................
Part # 0C8127
Battery
Requirement
at
-17.8" C (0" F) .......................
Group
26/26R
12 Volts and
525 Cold<ranking
Amperes
Mhlhnmn
Weight ...........................................................
487 Pounds
Output
Sound
Level (_ 23 ft (7m)
at fldl load ...................................................
71.5 db (A}
Normal
Operating
Ran,_e ...........................
-20°F (-28.8"C)
to 104°E 140"C)
* Maxiiyll/ill
w_th_e
aIld
(;llrreza
are
Slit)jeer
to
_ti]d
lhl]ited
by
Slid]
l'z_<:tOrS
as fuel Btu
(;oIlteIlt,
aI]]l)ieI][
teI]]l)eratllre,
altitllde,
eI]_hle
power
alld
COn-
ditiom
etc.
Maximum
power
decreases
about
3.5
percent
fl_r each
lnOO
feet
above
sea
level:
and
also
will
deele_se
about
1 pereenl
for
each
6 '_ ¢
(IfY F )above i(¢ _( (60 _F).
+ Total
current
i_l hvo
separate
circuits.
Current
in each
circuit
must
not
exceed the value staledh>r 240V
1.6.2
ENGINE
Type of Engine
......................................................
GT-990
Nmnber
of Cylinders
......................................................
2
Rated Horsepower
..................................
30 % 3,¢;00 rpm
Displacement
..........................................................
992ec
Cylinder
Block .....................
Alumimmi
w/Cast
Iron Sleeve
_&dve Arrangement
..................................
Overhead
Valves
Ignition
System
..............................
Solid-state
w/Magneto
Reeonimended
Spark
Plug ...................................
0D4529
Spark
Plug Gap ............................
0.508
mm (0.020
inch)
Compression
Ratio ...................................................
9.5:1
Starter
....................................................................
12Vdc
Oil Capacity
Including
Filter ....................
Approx.
1.7 Qts
Recommended
Oil Filter ...........................
Part # 070185
Recommended
Air Filter ...........................
Part # 0C8127
Operating
RPM ........................................................
3,600
1o7
FUEL REQUIREMENTS
AND RECOMMENDATIONS
With
LP gas,
use
only
the
vapor
withdrawal
sys-
tem.
Tllis
type
of system
uses
the
vapors
%treed
above
tile liquid
lilel in tile storage
tank.
The
engine
has
been
fitted
witll
a fllel
earburetion
system
that
meets
tile
specifications
of the
1997
California
Air
Resources
Board
for
tamper=proof
dual
fllel systems.
The
unit
will run
on natural
gas or
LP gas,
but
it has
been
factory
set to run
on natural
gas.
Should
tile
primary
ihel
need
to be changed
to
LP gas, the fllel system
needs
to be reeonfigured.
See
instructions
in the
"Reeonfiguring
the
iSlel
Systenf'
seetion.
Recommended
fuels
should
lmve
a Btu
content
of at
least
1,000
Btus
per
cubic
loot
for natural
gas;
or at
least
2,520
Btus
per
cubic
toot
lot
LP gas.
Ask
the
fllel supplier
for tile Btu
content
of the thee
Required
fllel pressure
for natural
gas is 5 inches
to 7 inches
water
column
(0.18
to 0.25
psi);
and
for liquid
propane,
11 inches
to 14 inches
of water
column
(0.4 to 0.5 psi).
NOTE:
Any piping
used
to connect
the generator
to the
fuel
supply
should
be of adequate
size
to ensure
the
fuel
pressure
NEVER
drops
below
4 inches
water
column
for natural
gas or 10 inches
water
column
for liquid
propane
for all load ranges.
1o8
FUEL CONSUMPTION
Model
#
Nat. Gas {*}
LP Vapor
{**}
1/2 Load
Full Load
1/2 Load
Full Load
05207
156
220
1.58/58
2,40/88
* Nalmal
_as
is in cubic
feet
per
hour.
** LP is in gallons
per
hour/cubi(
feet
per
hour.
** _ Values
_ivell
al-e
at)t)l
OXillla(e.
Gaseous
fuels such as natural
gas and liquid
propane
(LP) gas are highly
explosive.
Even the
slightest
spark
can ignite
such fuels and cause
an explosion.
No leakage of fuel is permitted.
NaturM gas, which
is lighter
than
air, tends
to
collect in high areas. LP gas is heavier than air
and tends to settle in low areas.
6