Program The Vfd For 3 Discrete Indoor Fan Speeds - Carrier WeatherExpert 48LC Installation Instructions Manual

Single package rooftop gas heat/electric cooling unit with puronr (r ---410a) refrigerant size: 07
Hide thumbs Also See for WeatherExpert 48LC:
Table of Contents

Advertisement

Female Connector -
connect to back of
VFD Remote Keypad
Fig. 63 - - VFD Remote Keypad Cable

Program the VFD for 3 Discrete Indoor Fan Speeds

IMPORTANT: 48LC 07 units are programmed at the
factory for 3 discrete indoor fan speeds. The following
procedure is only to be used to recover this function
after an event such as a system crash.
NOTE: This procedure requires use of the VFD Keypad
which is included as part of the field- - installed
Multi- - Speed VFD display kit (PN: CRDISKIT002A00). If
the VFD keypad is not already installed, install it. See
"Connecting the Keypad to the VFD" for details.
Select language
[0] English
SETUP 1
Status
Menu
Com.
On
Warn.
Alarm
Hand
On
Fig. 64 - - Keypad with Power Up Screen Displayed
Male Connector -
connect to VFD
Front Panel
English
Quick
Main
Menu
Menu
OK
Off
Auto
Reset
On
To program the VFD for 3 discreet indoor fan motor
speeds:
1. At Power- - Up:
At the first power up the LCD displays the Select
Language screen. The default setting is English. To
change the language, press the OK key and use the Y
and B keys to scroll to the desired language and then
press OK.
2. Selecting Regional Settings:
a. Press the Off Reset key.
b. Press the Menu key to move the B(triangle
icon) so it is positioned over Main Menu. The
display show the following - -
c. Press the OK key, the display changes to - -
d. With the top row highlighted, press OK. The
display changes to - -
C13118
NOTE: If English is not the desired language press OK,
select the desired language and press OK again.
e. Press B(Down Arrow key) once; the display
changes to - -
f. Press OK; the [0] is now highlighted.
g. Press B(Down Arrow) key once; the display
changes to - -
h. Press OK
NOTE: If the Alarm 060 appears, follow Step 3 to clear
the alarm. Make sure to press Off Reset when done. If
there is no alarm, continue at Step 4.
3. Clearing Alarm 060: External Interlock:
a. Press the Menu key twice to position the B(tri-
angle icon) over Main Menu; the display
changes to - -
b. Press the B(Down Arrow) key until the follow-
ing display appears - -
c. Press OK. The display changes to - -
C13119
57
0--- ** Operation / Display
1--- ** Load and Motor
0--- 0* Basic Settings
0--- 1* Set--- up Operations
0--- 01 Language
[0] English
0--- 03 Regional Settings
[0] International
0--- 03 Regional Settings
[1] North America
0--- ** Operation / Display
1--- ** Load and Motor
4--- ** Limits / Warnings
5--- ** Digital In/Out
5--- 0* Digital I/O mode
5--- 1* Digital Inputs